Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 63

Advertising
background image

63

S

0815

0815 SW REQ. VAL

Switching between required value 1 and 2

Setpoint 1

Possible settings:

- Setpoint 1

- Setpoint 2

- Switch Dig 1

- Switch Dig 2

- Switch Dig 3

- Switch Dig 4

Setpoint 1:

Only required value 1 is active (No switching possible)

Setpoint 2:

Only required value 2 is active (No switching possible)

Switch Dig 1:

Manual switching by closing digital input 1 (X3/9-10)

Switch Dig 2:

Manual switching by closing digital input 2 (X3/6-10)

Switch Dig 3:

Manual switching by closing digital input 3 (X3/5-10)

Switch Dig 4:

Manual switching by closing digital input 4 (X3/15-16)

0820

0820 REQ.VAL.1

Required value 1 (digital)

XX.X PSI

Possible settings:

0.0 – to the pre selected sensor range

0825

0825 REQ.VAL.2

Required value 2 (digital)

XX.X PSI

Possible settings:

0.0 – to the pre selected sensor range

Set the desired required value with either

or

.

This pre-selected required value is active in all modes except Actuator if parameter C.REQ.VAL.1 [0805] or
C.REQ.VAL.2 [0810] is set to digital, and parameter SW REQ.VAL. [0815] is set to setpoint 1/2 or the RE-
QUIRED VALUE 1/2 is selected via digital input.

This pre-selected required value could also be taken over in the main menu with parameter REQUIRED
VAL. [02] if the current required value is active.

0830

0830 ACTUAT.FRQ 1

Required frequency 1 for actuator

XX.X Hz

Possible settings:

0.0 – MAX. FREQ. [0245]

0835

0835 ACTUAT.FRQ 2

Required frequency 2 for actuator

XX.X Hz

Possible settings:

0.0 – MAX. FREQ. [0245]

Set the frequency with either

or

.

The selected frequency in this parameter is only active in the actuator mode if parameter C.REQ.VAL.1
[0805] or C.REQ.VAL.2 [0810] is set to digital, and parameter SW REQ.VAL [0815] is set to setpoint 1/2 or
the ACTUATOR FREQUENCY 1/2 is selected via digital input.

proGraMMinG