• Incoming pressure or minimum level

too low

lacK oF Water

Low water contact

• Bridge X3/11-12, if there is no ext.

error 21

(X3/11-12) is opened

low water protection

(only active if motor is running) • Adjust Parameter DELAY TIME [0610]

if the failure happens only for a

short time

reset:

• Automatically if low water contact (X3/11-12) is closed!

Defined value of parameter

• Check booster unit, adjust

Min. tHresHold

MIN.THRESHOLD [0605] was

parameter DELAY TIME [0610]

error 22

not reached during the

• Parameter ERROR RESET [0615] set

preselected DELAY-TIME [0610] to ON, to enable 5 restarts

Sensor signal on terminals

• ACTUAL VALUE signal (pressure

Failure sensor 1

X3/2 <4mA

transducer) faulty

Active Sensor:

• Poor connection

act. Val. sensor 1

WARNING (20 sec.)-> ERROR

• Sensor or cable fault

error 23

Non-active sensor: WARNING

• check configuration of the sensors

in submenu SENSORS [0400]

Sensor signal on terminals

• ACTUAL VALUE signal (pressure

Failure sensor 2

X3/2 <4mA

transducer) faulty

Active Sensor:

• Poor connection

act. Val. sensor 2

WARNING (20 sec.)-> ERROR

• Sensor or cable fault

error 24

Non-active sensor: WARNING

• check configuration of the sensors

in submenu SENSORS [0400]

Current signal input of required

• Check external analogue signal on

setpoint 1 i<4ma

values is active, but no signal

terminals X3/17-18

4-20mA is connected

• Check configuration of the required

setpoint 1 i<4ma

WARNING (20 sec.)-> ERROR

values in Submenu REQUIRED

error 25

VALUES [0800]

Current signal input of required

• Check external analogue signal on

setpoint 2 i<4ma

values is active, but no signal

terminals X3/22-23

4-20mA is connected

• Check configuration of the required

setpoint 2 i<4ma

WARNING (20 sec.)-> ERROR

values in Submenu REQUIRED

error 26

VALUES [0800]

• Cut off power supply for > 60 seconds.

reset:

• Manual reset by closing external ON/OFF (Terminals X3/7-8)

• Manual reset by pressing and simultaneously for about 5 seconds

• Auto-reset possible if ERROR-RESET [0615] is set to ON

Failure MessaGes