10.3 internal errors

To remove the following errors cut the power supply for >60 seconds. If the error message is still shown on the
display, contact customer service and provide a detailed description of the error.

internal errors

error-message on the display - red led on

ERROR 1

EEPROM-ERROR

Reset - after repeated error-message

(data block malfunction)

change control card

• Check push buttons,

Button error

• Display-board may be defective

ERROR 4

(e.g.: jammed key)

• Assure drive cover securely attached

to base with no interference (pinched

wires, debris, etc.)

ERROR 5

EPROM-error

Reset - after repeated error-message

(Checksum error)

change control card

ERROR 6

Program error:

Reset - after repeated error-message

Watchdog error

change control card

ERROR 7

Program error:

Reset - after repeated error-message

Processor pulse error

change control card

• Check installation of cables,

connection of the screen and

CODE ERROR

Code error:

balanced power supply.

invalid processor command

• Check earth/ground.

• Install additional inductances for

the signal-cables (e.g. ferrites).

examples:

Booster unit

problem: HYdroVar will not stop
cause:

check:

• Demand exceeds pump capacity

• Check pipes and valves

• Pre-charge pressure in pressure tank

• Set WINDOW [0310] (< 10%) and

• Incorrect setting of WINDOW and

HYSTERESIS [0315] (80-50%)

RAMP HYSTERESIS

• Set RAMP 2 [0220] to 4...13 sec.

• Shut down ramp too slow

• MINIMUM FREQUENCY [0250] should be

• Suction line too long

activated for pressure increase at 0 demand

Failure MessaGes