Electrical installation and wiring, Fused disconnect box, Customer supplied – Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 20

Advertising
background image

20

Fused disconnect Box:

GND

L1

L2

1

3

5

2

4

6

SINGLE

PHASE

CUSTOMER SUPPLIED

VOLTAGE

DISCONNECT

FUSE BLOCK

12 AWG

12 AWG

HYDROVAR

GND

PE

U1

V1

W1

U2

V2

W2

16 AWG

GND

MTR

MOTOR

CUSTOMER SUPPLIED

GND

L1

L3

1

3

5

2

4

6

THREE

PHASE

CUSTOMER SUPPLIED

VOLTAGE

DISCONNECT

FUSE BLOCK

12 AWG

12 AWG

HYDROVAR

GND

PE

U1

V1

W1

U2

V2

W2

16 AWG

GND

MTR

MOTOR

CUSTOMER SUPPLIED

L2

12 AWG

electrical installation and WirinG

disconnect

part number

input

Voltage

disconnect

Hp / aMp

rating

Wire

range

tightening

torque

Fuse

supplier

aMp

rating

part

number

Voltage

rating

HFD512C1

230/1/60

OT25F3

2 HP / 25A

#18-

8AWG

7 IN/LB

Bussman

20

KTK-R-20

600V

HFD512E1

230/1/60

OT40F3

3 HP / 40A

#18-

8AWG

7 IN/LB

Bussman

30

KTK-R-30

600V

HFD534A1

460/3/60

OT16F3

3 HP / 16A

#18-

8AWG

7 IN/LB

Bussman

10

KTK-R-10

600V

HFD534B1

460/3/60

OT16F3

3 HP / 16A

#18-

8AWG

7 IN/LB

Bussman

15

KTK-R-15

600V

HFD534C1

460/3/60

OT25F3

3 HP / 25A

#18-

8AWG

7 IN/LB

Bussman

20

KTK-R-20

600V

HFD534C2

460/3/60

OT25F3

3 HP / 25A

#18-

8AWG

7 IN/LB

Bussman

20

KTK-R-20

600V

HFD534E2

460/3/60

OT40F3

3 HP / 40A

#18-

8AWG

7 IN/LB

Bussman

30

KTK-R-30

600V

note: Recommended protection (not included with drive only). This fused disconnect is available as part of the PHV series packaged
Hydrovar, see price book.

Advertising