Programming – Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 53

Advertising
background image

53

G

G

H

Q

A

C

0

1

2

3

4

B

f = 100%

%f

%f

%f

G

0320

0320 REG. MODE

Regulation mode

normal

Possible settings:

normal, inverse

normal: Speed is increased with falling actual value signals. (e.g.: control at constant output pressure)
inverse: Speed is reduced with falling actual value signal. (e.g.: control at constant suction pressure or at
constant level on the suction side)

0325

0325 FRQ. LIFT

Frequency limit for required lift value

30.0 Hz

Possible settings:

0.0 Hz – 70.0 Hz

Control according to a system curve (increase of the set pressure, depending on the flow rate/speed to
cover friction losses).
The setting determines the output-frequency where the set pressure starts to be increased. The right set-
ting should be equal to the frequency when the pump reaches the set pressure at zero flow (Can be deter-
mined by using the JOG MODE [0305]).

0330

0330 LIFT AMOUNT

Lift amount for required lift value

0.0 %

Possible settings:

0.0 – 200.0%

This value states how much the set value should be continually increased, till the maximum speed (maxi-
mum volume) is reached.

application example:

1) Enter the set pressure (see main menu

parameter REQ. VAL [02]).

2) Find out the frequency where set pres-

sure is reached at zero demand (use JOG
MODE [0305]) and set the value in param-
eter FREQU. LIFTING.

3) Set desired lift at maximum speed in % of

the set pressure in the parameter LIFT-
AMOUNT [0330].

A … set pressure
B … window
C … lift intensity in % of set pressure

proGraMMinG