Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 30

Advertising
background image

30

additional power supply

** max. 100 mA

current signal input (required val. 2) 0-20mA / 4-20mA [Ri=50Ω]

To determine the required value or the offset

analogue output 2 4-20mA

analogue output 1 0-10 VDC

current signal input (required val. 1) 0-20mA / 4-20mA [Ri=50Ω]

To determine the required value or the offset

Voltage signal input (required value 2) 0-10 VDC

*diG 4

To determine the required value or the offset

Voltage signal input (required value 1) 0-10 VDC

To determine the required value or the offset

low water

incoming pressure switch or water level switch required (or jumper)

Configurable digital input 1

DIG 1

for switching between 2 required values or sensors

external on/oFF (e-stop) (Connect through switch or jumper)

actual-value-voltage input sensor 1 0-10 VDC

*diG 2

actual-value-voltage input sensor 2 0-10 VDC

*diG 3

actual-value-current input sensor 2 0-20mA / 4-20mA [Ri=50Ω]

sensor supply voltage ** maximum 100 mA

actual value current input sensor 1 0-20mA / 4-20mA [Ri=50Ω]

Ground

* Terminals X3/5 and 6 can be used as actual value voltage input and also as digital input. Also the

voltage signal input on terminal X3/15 can be used as digital input.

** X3/3 and X3/24 → Σ maximum 100mA

X3

X3

24 +24V

23

22

21

20

19 +10V

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3 +24V

2

1

electrical installation and WirinG