0415 SENSOR TYPE

Selection of the sensor type and input terminal

4 – 20mA

Possible settings:

- analog I 4-20mA - analog I 0-20mA - analog U 0-10V

For choosing the correct sensor input.

sensor type:

terminals:

- analog I 4-20mA

The actual value is represented by a current

X3/2 -> Sensor 1

- analog I 0-20mA

signal connected to following terminals:

* X3/4 -> Sensor 2

- analog U 0-10V

The actual value is given from a voltage signal

X3/6 -> Sensor 1

connected to following terminals:

* X3/5 -> Sensor 2

* … Sensor 2 is not available for the Single Inverter configuration

0420

0420 SENS. RANGE

Sensor range

20mA = 300 PSI

Possible settings:

0.00 – 10000

Determines the end value (=20mA or 10V) of the connected sensor.
The maximum sensor range -> 20mA = 100% of the sensor range.

example:
300 PSI pressure sensor

=>

20mA = 300 PSI

0425

0425 SENS. CURVE

Sensor curve

linear

Possible settings:

linear, quadratic

Internal calculation based on the actual value.
possible setting and its application:
linear: Pressure control, differential pressure control, level, temperature and flow control (inductive or

mechanical).

Quadratic: Flow control using an orifice plate together with a differential pressure sensor.

0430

0430 SENS 1 CAL 0

Sensor 1 zero point calibration

0% = actual value

Possible settings:

- 10% up to +10%

This parameter is used to calibrate the minimum value of Sensor 1. After setting the dimension unit and the
sensor range the zero point for this sensor can be adjusted. Adjustable range between -10 % and +10 %.

0435

0435 SENS 1 CAL X

Sensor 1 upper range value calibration

0% = actual value

Possible settings:

- 10% up to +10%

To set the calibration for the upper range value of sensor 1. After setting the dimension unit and sensor
range, the upper range value can be adjusted between -10 and +10%.

proGraMMinG