1100 1100 suBMenu setup

1110

1110 FACTORY SET

Restores the HV to factory setting

USA

Possible settings:

EUROPE, USA

To restore the HYDROVAR to factory settings select Europe or USA.
For reset press button until “DONE” appears.

1120

1120 PASSWORD 2

Enter password by pressing

or

0000

The below mentioned parameters are available after entering the correct password!
For more information, contact your local distributor!

1125

1125 CLR ERRORS

Clear error memory of selected unit

UNIT X

or on ALL units (Cascade Serial/Synchron)

Possible settings:

1 – 8, ALL

To clear the error memory either (1-8) for one specific unit or ALL for all units, can be selected.
For reset press button till “RESET” appears.

1130

1130 CLR MOTORH.

Clear motor hours for selected unit

UNIT X

or on ALL units (Cascade Serial/Synchron)

Possible settings:

1 – 8, ALL

Set desired unit where the Motor Hours should be cleared (or ALL) and press button until “RESET”
appears.

1135

1135 CLR OPERAT.

Clear operation time

Press 3 sec.

The operation time indicates the total time the HYDROVAR is already connected to power supply. For reset
the operation time of the current HYDROVAR press button till “RESET” appears.

1200

1200 suBMenu

rs485-interFace

user interface
The following 3 Parameters are necessary for communication between the HYDROVAR and an external
device (e.g. PLC) via standardized Modbus-protocol. Set desired address, Baudrate and Format according
to the system requirements.

1205

1205 ADDRESS

Set desired address for the user interface

1

Possible settings:

1 - 247

proGraMMinG