Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 66

Advertising
background image

66

S

G

G

G

G

1000

1000 suBMenu

test run

1005

1005 TEST RUN

Automatic test run

after 100 hrs

Possible settings:

OFF – 100 h.

The Automatic Test Run starts the pump when it has not run for the number of hours set.

Test Run Time, Frequency and Boost can be selected in the parameters below.

To disable the automatic test run, press

until “OFF” appears on the display.

the test run is only active when the HYdroVar is stopped because of low/no demand and external

on/oFF (e-stop) contact (x3/7-8) is closed!

1010

1010 TESTRUN FRQ.

Frequency for manual and automatic test run

30.0 Hz

Possible settings:

0 – Fmax

1015

1015 TESTR. BOOST

Setting the motor starting voltage boost in %

10.0 %

of rated input voltage

Possible settings:

0 – 25% of maximum input voltage

1020

1020 TESTRUN TIME

Test Run time

5 sec

Possible settings:

0-180 sec.

1025

1025 SEL. DEVICE

Select Inverter for manual test run

01

Possible settings:

01-08

1030

1030 TESTRUN MAN

Manual Test Run, Confirm test run for selected unit

Press 3 sec.

Perform a manual Test Run for one selected unit. (Even fixed speed pumps in Cascade Relay Mode can be
included in the test run function.)

By pressing button for approximately 3 seconds a test run will be started.