10.2 Master / single inverter

Each error is shown on the display in plain text and saved in the error memory.

The errors can be reset automatically (depending on the setting in parameter ERROR-RESET [0615]) or manually
in following ways:
• cutting the power supply for > 60 seconds
• pressing and simultaneously for about 5 seconds
• open and close the External ON/OFF (Terminals X3/7-8)

no error-message on the display

error

probable cause

Measure

no AUTOSTART after

Parameter AUTOSTART [08] is

Check parameter AUTOSTART [08]

power failure

set to “OFF”

No operation when system

Pressure higher than the start

Check parameter START VALUE [04]

pressure < set pressure

value or REGULATION MODE

and/or REGULATION MODE [0320]

has been changed to INVERSE.

error-message on the display

error

probable cause

Measure

• check connection-terminals of the

oVercurrent

Current rise at the output

HYDROVAR

error 11

too high

• check the connection-terminal of

the motor and the motor-cable

• check the windings of the motor

reset:

• The power supply for >60 seconds.

• Automatic Error-reset not possible for this failure!

Failure MessaGes