oFF: All parameters in the MAIN menu (only) can be changed without entering the password.
on: If the LOCK FUNCTION is activated, no changes can be made in any parameter without first entering
the password. The HYDROVAR can be started and stopped with the up/down arrows. To change the set
value, the LOCK FUNCTION must be set to OFF.

0120

0120 DISP. CONTR.

Display Contrast

75 %

Possible settings:

10 – 100%

Can be adjusted between 10 - 100%, to improve the display.

0125

0125 DISP. BRIGHT

Display Brightness

100 %

Possible settings:

10 – 100%

The backlight intensity of the display can be adjusted.

0200

0200 suBMenu conF

inVerter

0202

0202 SOFTWARE

Software version of the control board

HV V01.3

0202

0202 SW RD V01.0

Software version of the Remote display (RD) (not available) and

HV V01.3

the control board (HV)

0203

0203 SET VER.INV

Activate additional settings. Contact factory to use.

sel:01

act:01

Possible settings:

00 - 02

Activates skip frequency parameter and current limit functions. These functions are not commonly used,
and may have undesirable effects. They should only be used to solve application problems in the field.
Press and hold the right arrow for 5 seconds to activate the function, and "Done" is displayed.The following
parameters [0285], [0286], [0290] and [0291] are added to the parameter list.)

Setting 00: all units with production date prior 05/2008
Setting 01: Basic 2 - 5 HP (on control board software V01.3)
Setting 02: Basic 7.5 - 15 HP (on control board software V01.3)

0205

0205 MAX. UNITS

Maximum number of units

06

Possible settings:

1 - 8

Select: The maximum number of units that can be set up as a multi-pump system.

0210

0210 INVERTER

Selection of the HYDROVAR address for parameterizing

ALL

Possible settings:

ALL, 1-8

G

proGraMMinG