x3 digital and analogue i/o

X3/

1 GND, electronic ground

2 Actual value current input sensor 1

0-20mA / 4-20mA [Ri=50Ω]

3 Power supply for external sensors

24VDC, ** max. 100mA

4 Actual value current input sensor 2

0-20mA / 4-20mA [Ri=50Ω]

5 Actual value voltage input sensor 2

*DI 2

0-10 VDC

6 Actual value voltage input sensor 1

*DI 1

0-10 VDC

7 External ON/OFF (E-Stop)

***

Switch or jumper

8 GND, electronic ground

9 Configurable digital input 1

Switch between DI 1

10 GND, electronic ground

and DI 2

11 Low water

***

Switch or jumper

12 GND, electronic ground

13 Voltage signal input (required value 1)

(Offset)

0-10VDC

14 GND, electronic ground

15 Voltage signal input (required value 2)

*Dig 3

(Offset)

0-10VDC

16 GND, electronic ground

17 GND, electronic ground

18 Current signal input (required value 1)

(Offset) 0-20mA / 4-20mA

[Ri=50Ω]

19 +10V internal ref. for analogue output

10,00VDC, max. 3mA

20 Analogue output 1

0-10VDC, max. 2mA

21 Analogue output 2

4-20mA

22 GND, electronic ground

23 Current signal input (required value 2)

(Offset)

0-20mA / 4-20mA [Ri=50Ω]

24 +24V power supply for control inputs

24VDC, ** max. 100mA

* Terminals 5 and 6 can be used as actual value voltage input and also as digital input. Also the

voltage signal input on terminal X3/15 can be used as digital input.

** X3/3 and X3/24 → maximum 100mA

*** Must be connected through a switch or a jumper

(Offset) These terminals can be used as required value or offset signal input. Configuration: see

submenu REQUIRED VALUES [0800] and submenu OFFSET [0900].

electrical installation and WirinG