Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 62

Advertising
background image

62

S

S

S

0800

0800 suBMenu

reQuired Values

0805

0805 C.REQ.VAL 1

Configuration required value 1

digital

Possible settings:

- digital

- analog U 0-10V

- analog I 0-20mA

- analog I 4-20mA

digital

The internal required value 1 is used.

Setting in the main menu in Parameter 02 or parameter [0820].

analog u=0 – 10V

The required value 1 is determined by the value of a voltage signal

(0 – 10V) connected to terminals X3/13- X3/14 (GND).

The required value 1 is determined by the value of a current signal

analog i=0 – 20ma

(4 – 20mA or 0 – 20mA) connected to terminals X3/18- X3/17

(GND).

notice: If the incoming current signal drops below 4mA (4-20mA

analog i=4 – 20ma

setting), a warning message is shown on the display. If the failure is

still active after 20 seconds, an error message will be shown.

The changeover between the 1st and the 2nd required value can be done either internally or externally via
the digital inputs. With the following parameters the source of the required values and the change over can
be configured.

0810

0810 C.REQ.VAL 2

Configuration required value 2

OFF

Possible settings:

- OFF

- digital

- analog U 0-10V

- analog I 0-20mA

- analog I 4-20mA

oFF

Required value 2 is not used.

digital

The internal required value 2 is used.

Setting in the main menu in Parameter 02 or Parameter [0825].

analog u 0 – 10V

The required value 2 is determined by the value of a voltage

signal (0 – 10V) connected to terminals X3/15- X3/16 (GND).

The required value 2 is determined by the value of a current

analog i 0 – 20ma

signal (4 – 20mA or 0 – 20mA) connected to terminals

X3/23- X3/22 (GND).

notice: If the incoming current signal falls below 4mA (4-20mA

analog i 4 – 20ma

setting), a warning message is shown on the display. If the failure is

still active after 20 seconds, an error message will be shown.

proGraMMinG