4. Getting Started

Fieldbus is fully dependent upon digital

communication protocol and differs in operation

from conventional 4 to 20 mA transmission and

the BRAIN or HART communication protocol. It is

recommended that novice users use field devices

in accordance with the procedures described in this

section. The procedures assume that field devices

will be set up on a bench or an instrument shop.

4.1 Connection of Devices

The following instruments are required for use with

Fieldbus devices:

• Power supply:

Fieldbus requires a dedicated power supply. It

is recommended that current capacity be well

over the total value of the maximum current

consumed by all devices (including the host).

Conventional DC current cannot be used as is.

• Terminator:

Fieldbus requires two terminators. Refer to

the supplier for details of terminators that are

attached to the host.

• Field devices:

Connect Fieldbus communication type YTA320.

Two or more YTA320 devices or other devices

can be connected.

• Host:

Used for accessing field devices. A

dedicated host (such as DCS) is used for

an instrumentation line while dedicated

communication tools are used for experimental

purposes. For operation of the host, refer to

the instruction manual for each host. No details

of the host are explained in the rest of this

material.

• Cable:

Used for connecting devices. Refer to “Fieldbus

Technical Information” (TI 38K3A01-01E) for

details of instrumentation cabling. If the total

length of the cable is in a range of 2 to 3 meters

for laboratory or other experimental use, the

following simplified cable (a twisted pair wire

with a cross section of 0.9 mm2 or more and

cycle period of within 5 cm (2 inches) may be

used. Termination processing depends on the

type of device being deployed. For YTA, use an

M4 screw terminal claw. Some hosts require a

connector.

Refer to Yokogawa when making arrangements to

purchase the recommended equipment.
Connect the devices as shown in Figure 4.1.

Connect the terminators at both ends of the

trunk, with a minimum length of the spur laid for

connection.
The polarity of signal and power must be

maintained.

YTA320

Fieldbus power

supply

Terminator

Terminator

HOST

F0401.ai

Figure 4.1

Cabling

NOTE

No CHECK terminal is used for Fieldbus

communication YTA. Do not connect the field

indicator and check meter. Use the instrument

with the short-bar being installed between (-)

terminal and the CHECK terminal.

Before using a Fieldbus configuration tool other

than the existing host, confirm it does not affect the

loop functionality in which all devices are already

installed in operation. Disconnect the relevant

control loop from the bus if necessary.

IMPORTANT

Connecting a Fieldbus configuration tool to a loop

with its existing host may cause communication

data scrambles resulting in a functional disorder

or a system failure.