<6. In-process Operation>

6-3

IM 01C50T02-01E

Following figure shows the items shown on a

display.

F0603.ai

(5)

(3)

(2)

(1)

(4)

Figure 6.3

LCD Display

Five-digit LCD Display (1)

Shows Output value(OUT) of AI block, Address,

and Error Codes(AL XXX). Shows "-----" when

the communication has not been established,

for example immediately after power on, or

when AI block is not scheduled.

Unit Display (2)

Unit of OUT value displayed on the Five-digit

LCD.

Dot-matrix Display (3)

Shows name of the AI block whose OUT value

is displayed on the five-digit display(AI1, AI2,

AI3, AI4) and status of the OUT signal(Good,

Bad, Uncertain). Shows 'Stop' when the

communication has not been established, for

example immediately after power on, or when

AI block is not scheduled. Shows 'FAIL'. when a

hardware error is detected,

Signal type diplay (4)

Shows the type of the signal which is assigened

for AI block. (Sensor1, Sensor2, Terminal

Temperature, Average, Differential). For Sensor

back-up value, shows the sensor which is used

as current input value.

Bar-graph (5)

Always shows output value(OUT) of AI1.

Items are shown in cyclic way. An example of

display is shown below.

Parameters in Transducer block

DISPLAY_AI_OUT

= AI1, AI2

DISPLAY_ERROR

= SHOW

DISPLAY_WARNING = INHIBIT

DISPLAY_ADDR

= SHOW

CHANNEL of AI1, AI2 block

CHANNEL of AI1 = 1 (Sensor1)

CHANNEL of AI2 = 2 (Sensor2)

Five-digit LCD

AI1 OUT

AI1 OUT

Error Code

Node Address

Node Address

( 50.00 °C )

( 50.00 °C )

( AL021 )

( 243 )

( 243 )

Dot-matrix

Block Name

Status of Signal

[None]

Node

Addres

Display :

(AI1)

(Bad)

(Nod)

(Adr)

F0604.ai

#

[ Overview ]

In the example below, parameters are set as shown in the box in the right.

As the transducer block and the resource block are currently in O/S mode, error codes

'AL021' and 'AL022' are shown in turn, and the status of OUT for both AI1 and AI2 appears

as 'Bad'. If the status of OUT is 'good', 'G.D' is shown in place. If it is 'uncertain', 'UnC' is

displayed.

#

Five-digit LCD

AI2 OUT

AI2 OUT

Error Code

Node Address

Node Address

( 60.80 °C )

( 60.80 °C )

( AL022 )

( 243 )

( 243 )

Dot-matrix

Block Name

Status of Signal

[None]

Node

Addres

Display :

(AI2)

(Bad)

(Nod)

(Adr)

Figure 6.4

Display Example