<Appendix 1. List of Parameters for Each Block of the YTA>

A1-5

IM 01C50T02-01E

Relative

Index

Index

Parameter

Name

Factory

Default

Write

Mode

Explanation

AI1 AI2 AI3 AI4

21

4021 4121 4221 4321 BLOCK_ALM —

The block alarm is used for all

configuration, hardware, connection failure

or system problems in the block. The cause

of the alert is entered in the subcode field.

The first alert to become active will set the

Active status in the Status attribute. As

soon as the Unreported status is cleared by

the alert reporting task, another block alert

may be reported without clearing the Active

status, if the subcode has changed.

22

4022 4122 4222 4322 ALARM_

SUM

Enable

The current alert status, unacknowledged

states, unreported states, and disabled

states of the alarms associated with the

function block.

23

4023 4123 4223 4323 ACK_

OPTION

0xfff : unack Auto

Selection of whether alarms associated

with the block will be automatically

acknowledged.

24

4024 4124 4224 4324 ALARM_HYS 0.5%

Auto

Amount the PV must return within the alarm

limits before the alarm condition clears.

Alarm Hysteresis is expressed as a percent

of the PV span.

25

4025 4125 4225 4325 HI_HI_PRI

0

Auto

Priority of the high high alarm.

26

4026 4126 4226 4326 HI_HI_LIM

+INF

Auto

The setting for high high alarm in

engineering units.

27

4027 4127 4227 4327 HI_PRI

0

Auto

Priority of the high alarm.

28

4028 4128 4228 4328 HI_LIM

+INF

Auto

The setting for high alarm in engineering

units.

29

4029 4129 4229 4329 LO_PRI

0

Auto

Priority of the low alarm.

30

4030 4130 4230 4330 LO_LIM

–INF

Auto

The setting for the low alarm in engineering

units.

31

4031 4131 4231 4331 LO_LO_PRI 0

Auto

Priority of the low low alarm.

32

4032 4132 4232 4332 LO_LO_LIM –INF

Auto

The setting of the low low alarm in

engineering units.

33

4033 4133 4233 4333 HI_HI_ALM

The status for high high alarm and its

associated time stamp.

34

4034 4134 4234 4334 HI_ALM

The status for high alarm and its associated

time stamp.

35

4035 4135 4235 4335 LO_ALM

The status of the low alarm and its

associated time stamp.

36

4036 4136 4236 4336 LO_LO_ALM —

The status of the low low alarm and its

associated time stamp.

A1.3 Dl Function Block

Relative

Index

Index

Parameter

Name

Default

(factory setting)

Write

Description

DI1 DI2 DI3 DI4

0

6000 6100 6200 6300 BLOCK

HEADER

Block tag

= O/S

Information about this block, including the

block tag, DD revision, execution time. The

value for “Period of Execution” should be

larger than “Execution Time.”

1

6001 6101 6201 6301 ST_REV

0

Incremented when a change is made to

the parameter settings for the DI block to

indicate the revision level of the settings,

and used to see whether there is a change

in parameter settings.

2

6002 6102 6202 6302 TAG_DESC

Spaces

Universal parameter storing the

description of the tag.

3

6003 6103 6203 6303 STRATEGY

1

Universal parameter used by an upper-

level system to classify the function blocks.