A2.2 making and changing basic parameter settings, A2.3 setting up the transducer block, A2.2 – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 71: A2.3, A2-2, Important

Advertising
background image

<Appendix 2. Parameters for Basic Settings, and How to Make and Change the Settings>

A2-2

IM 01C50T02-01E

To Do This

Corresponding Parameters

Outline of Procedure

Set the output cut-off

levels

LOW_CUT

in each AI block

For each AI block, set the output cut-off level suitable for the

L_TYPE setting (= Direct, Indirect, or IndirectSQRT). The

output value will be cut off to 0 when it is below the value set in

LOW_CUT.

Set the time constants

of damping filters

PV_FTIME

of each of AI and DI blocks

For each AI block, set the time constant (in seconds) of the

first-order lag filter.
For each DI block, set the delay time in seconds.

Carry out simulations

for AI and DI blocks

SIMULATE

in each AI block

SIMULATE_D

in each DI block

Manually set input values and statuses for AI and DI blocks;

the blocks then carry out the specified actions with the

simulated input signals. This simulation function is useful for

loop checks and so on. See Section 6.3 for details.

Make LCD display

settings

DISPLAY_AI_OUT

DISPLAY_CYCLE in the

transducer block

Select the AI blocks whose output values you want to display

on the LCD and set the display refresh cycle. If the response

of the LCD is slow such as when used in a cold place, the

display refresh cycle needs to be adjusted.

Carry out an input

calibration

CAL_POINT_HI

CAL_POINT_LO

in the transducer block

Apply an input signal, vary the input signal level, and set the

upper and lower range limits corresponding to the 0% and

100% input levels. The output range can be set accurately

to the exact output signal levels generated by the user's

reference instrument.

A2.2 Making and Changing

Basic Parameter Settings

The figure below outlines the procedure to make

basic parameter settings and change them.
The method of accessing each parameter differs

depending on the configuration tool you use;
see the documentation for the configuration tool.

Access the parameter MODE_BLK in the function block

containing the parameter whose settings you want to

make or change.

Set the target mode(Note 1) in MODE_BLK to a mode

(Auto, Man, or O/S(Note 2)) in which write access to the

desired parameter is permitted.

Access the desired parameter.

Change the settings as appropriate.

Return the target mode in MODE_BLK to Auto. (Note 2)

IMPORTANT

Do not turn off the power to the YTA320

transmitter immediately after changing the

parameter settings.

If the power is turned off within 60 seconds after

making a change, the change is not saved and

the previous setting is restored.

Note 1: MODE_BLK is a universal parameter that indicates the

block operation conditions and is composed of actual

mode, target mode, permitted modes, and normal

mode.

Target: Used to set the mode that the block should

enter.

Actual: Indicates the current mode of the block.

Permit: Indicates all modes that the block can enter.

Normal: Indicates the mode in which the block should

be normally.

Note 2: The modes each block can enter are as follows.

Mode

AI

Block

DI

Block

Transducer

Block

Resource

Block

AUTO

(automatic)

MAN

(manual)

O/S

(out of service)

For the modes in which each parameter can be

written, see Appendix 1.

A2.3 Setting Up the Transducer

Block

To access the transducer’s functions specific to

the YTA320, the Device Description (DD) for the

YTA320 needs to be installed in the configuration

tool you use. For details on how to install the DD,

see Section 4.4.

Advertising