A1.5 unit and code, A1.5, A1-12 – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 69

Advertising
background image

<Appendix 1. List of Parameters for Each Block of the YTA>

A1-12

IM 01C50T02-01E

Relative

Index

Index

Parameter Name

Default

(factory setting)

Write

Description

100

2100 LIMSW_4_VALUE_

D

Indicates the value and status of limit switch 4.

101

2101 LIMSW_4_TARGET 0

O/S

Value to be monitored by limit switch 4. The

setting and the corresponding value are the

same as those for limit switch 1 (LIMSW_1_

TARGET).

102

2102 LIMSW_4

_SETPOINT

0

O/S

Threshold of switching on limit switch 4

103

2103 LIMSW_4_ACT

_DIRECTION

0 (high-limit switch) O/S

Type of limit switch 4. The setting and the

corresponding type are the same as those for

limit switch 1 (LIMSW_1_ACT_DIRECTION).

104

2104 LIMSW_4

_HYSTERESIS

0

O/S

Hysteresis of limit switch 4. Input of only a

positive number is valid.

105

2105 LIMSW_4_UNIT

Unit of LIMSW_4_SETPOINT and LIMSW_4_

HYSTERESIS

106

2106 DISPLAY_AI_OUT 0 (AI1 only)

Auto

Selects the AI block or blocks whose values

are to be displayed on the LCD:

0 = AI1

1 = AI2

2 = AI3

3 = AI4

4 = AI1, AI2

5 = AI1, AI2, AI3

6 = AI1, AI2, AI3, AI4

107

2107 DISPLAY_ERROR 0 (SHOW)

Auto

Whether to display error codes on the LCD:

0 = SHOW

1 = INHIBIT

108

2108 DISPLAY

_WARNING

1 (INHIBIT)

Auto

Whether to display warning codes on the LCD:

0 = SHOW

1 = INHIBIT

109

2109 DISPLAY

_ADDRESS

1 (INHIBIT)

Auto

Whether to display the device address on the LCD:

0 = SHOW

1 = INHIBIT

110

2110 DISPLAY_CYCLE

2

Auto

Display refresh cycle (2 to 255 seconds)

111

2111 WARNING_

ENABLE _1

Depends on the

specification upon

shipment

Auto

Switches on and off generation of warnings

corresponding to DEVICE_STATUS_5 of the

resource block.

112

2112 WARNING_

ENABLE _2

Depends on the

specification upon

shipment

Auto

Switches on and off generation of warnings

corresponding to DEVICE_STATUS_6 of the

resource block.

113

2113 WARNING_

ENABLE _3

Depends on the

specification upon

shipment

Auto

Switches on and off generation of warnings

corresponding to DEVICE_STATUS_7 of the

resource block.

114

2114 WARNING_

ENABLE _4

Depends on the

specification upon

shipment

Auto

Switches on and off generation of warnings

corresponding to DEVICE_STATUS_8 of the

resource block.

115

2115 MODEL

YTA320

Model code of the transmitter

116

2116 YTA_OPTION

Depends on the

specification upon

shipment

Option of the transmitter

A1.5 Unit and Code

Unit

Code

K

1000

°C

1001

°F (Note)

1002

°R (Note)

1003

mV

1243

ohm

1281

Note : Available only when option /D2 is specified.

Advertising