A1-6 – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 63

Advertising
background image

<Appendix 1. List of Parameters for Each Block of the YTA>

A1-6

IM 01C50T02-01E

Relative

Index

Index

Parameter

Name

Default

(factory setting)

Write

Description

DI1 DI2 DI3 DI4

4

6004 6104 6204 6304 ALERT_KEY 1

Universal parameter used as a key to

identify the point from which an alert is

issued; normally used by an upper-level

system to select alerts to provide to a

particular operator who covers a specific

area of the plant.

5

6005 6105 6205 6305 MODE_BLK

O/S

Universal parameter that indicates

the block operation conditions and is

composed of actual mode, target mode,

permitted modes, and normal mode.

6

6006 6106 6206 6306 BLOCK_ERR —

Indicates the error statuses related to the

block itself.

7

6007 6107 6207 6307 PV_D

Indicates the primary discrete value (or

the corresponding process value) used

to execute the specified actions, and the

status of that value.

8

6008 6108 6208 6308 OUT_D

Man

Indicates the output value and its status.

9

6009 6109 6209 6309 SIMULATE_D disabled

Used to determine whether to use the limit

switch signal input from the transducer

block or use the user-set value. When this

parameter is set to disable, the block uses

the actual input value and status.

10

6010 6110 6210 6310 XD_STATE

0

Index to the text describing the states

of the discrete value obtained from the

transducer, but not supported by YTA.

11

6011 6111 6211 6311 OUT_STATE 0

Index to the text describing the states of a

discrete output, but not supported by YTA.

12

6012 6112 6212 6312 GRANT_

DENY

0

Used to check whether various user

operations can be put into effective.

Before operations, in the GRANT

parameter component, set the bits

(to 1) corresponding to the intended

operations. After the operations, check

the DENY parameter component. If the

corresponding bits are not set (to 1) in

DENY, it proves that the corresponding

operation has been put into effective.

13

6013 6113 6213 6313 IO_OPTS

0

O/S

Settings for the I/O processing of the

block.

14

6014 6114 6214 6314 STATUS_

OPTS

0

O/S

Defines block actions depending on block

status conditions. In YTA, bit 0: Invert

alone is available.

15

6015 6115 6215 6315 CHANNEL

7/8/9/10

O/S

Defines the channel number of the

hardware channel connected to the

transducer block.

16

6016 6116 6216 6316 PV_FTIME

0 second

Time constant of filter for PV_D.

17

6017 6117 6217 6317 FIELD_VAL_

D

Status of limit switch signal obtained from

the transducer block

18

6018 6118 6218 6318 UPDATE_

EVT

Shows the contents of an update event

upon occurrence.

19

6019 6119 6219 6319 BLOCK_ALM —

Shows the contents of a block alarm upon

occurrence.

20

6020 6120 6220 6320 ALARM_SUM enable

Shows the alarm summary (current alarm

statuses, acknowledged/unacknowledged

states, masking states) for the DI block.

21

6021 6121 6221 6321 ACK_OPTION 0xffff: unack

Defines the priority of WRITE_ALM as well

as allows for notification to be disabled and

makes acknowledement unnecessary for

WRITE_ALM .

22

6022 6122 6222 6322 DISC_PRI

0

Priority order of discrete alarm

23

6023 6123 6223 6323 DISC_LIM

0

Input status of generating a discrete alarm

24

6024 6124 6224 6324 DISC_ALM

Status of discrete alarm

Advertising