<7. Errors and Warnings>

7-4

IM 01C50T02-01E

Code

Displayed

on LCD

Indication of DEVICE_

STATUS_#

Cause

Remedy

AL150

PID2 in Bypass active

The bypass action for PID2 is

active.

Reset BYPASS of PID2 to off.

AL160

Sensor1 Temp Too High

The temperature read by sensor

1 is higher than the specified high

limit.\

Check the adequacy of the measurement

temperature range and use the

appropriate sensor type.

AL161

Sensor1 Temp Too Low

The temperature read by sensor 1

is lower than the specified low limit.

Check the adequacy of the measurement

temperature range and use the

appropriate sensor type.

AL170

Sensor2 Temp Too High

The temperature read by sensor

2 is higher than the specified high

limit.

Check the adequacy of the measurement

temperature range and use the

appropriate sensor type.

AL171

Sensor2 Temp Too Low

The temperature read by sensor 2

is lower than the specified low limit.

Check the adequacy of the measurement

temperature range and use the

appropriate sensor type.

AL190

Stop Detection of Sensor

Burnout

Sensor burnout detection has been

stopped, and therefore a sensor

failure cannot be detected.

Set SENSOR_BURNOUT_DETECT to

0 (on).

AL191

Illegal Unit of AI1

The unit setting in XD_SCALE of

the AI1 block is illegal.

Correct the unit setting in XD_SCALE of

AI1 so that it matches the sensor type of

the input chosen for CHANNEL.

AL192

Illegal Unit of AI2

The unit setting in XD_SCALE of

the AI2 block is illegal.

Correct the unit setting in XD_SCALE of

AI2 so that it matches the sensor type of

the input chosen for CHANNEL.

AL193

Illegal Unit of AI3

The unit setting in XD_SCALE of

the AI3 block is illegal.

Correct the unit setting in XD_SCALE of

AI3 so that it matches the sensor type of

the input chosen for CHANNEL.

AL194

Illegal Unit of AI4

The unit setting in XD_SCALE of

the AI4 block is illegal.

Correct the unit setting in XD_SCALE of

AI4 so that it matches the sensor type of

the input chosen for CHANNEL.

AL198

Default Address Mode

The physical address is left as the

default.

Set the operable address.

Table 7.3

Troubleshooting When Actual in MODE_BLK of a Function Block Cannot Change from O/S

Presumed Cause

Remedy

The target mode of the function block in question is not set. Set the target mode of the block to Auto.
The actual mode of the resource block is O/S.

Set the target mode of the resource block to Auto.

Function block execution schedule is not set correctly.

Set up the schedule using a configuration tool or the like.