<7. Errors and Warnings>

7-1

IM 01C50T02-01E

7. Errors and Warnings

7.1 Error and Warning

Indications

Faults found as a result of self-diagnostics by a

YTA320 are identified as errors or warnings. Errors

are abnormalities in the physical device, such as a

hardware failure or communication error. Warnings

are problems in the parameter settings or abnormal

operation status of the device, such as the active

state of the bypass action and simulation mode,

in order to alert the user. The user can check the

errors and warnings currently occurring in a YTA320

with either of the following:

• Value (bit statuses) in DEVICE_STATUS_1 to

_8 of the resource block

• Error code displayed on the LCD (for a model

with a built-in LCD)

7.2 Checking with LCD

For a YTA320 with a built-in LCD, when an error

or warning occurs, the corresponding code is

displayed on the LCD. Codes AL001 to AL085

indicate errors, and AL100 and later indicate

warnings. The following shows the code, indication,

cause, and remedy for each of the errors and

warnings. Warnings and errors can be masked

independently by the user if desired (see Section

5.6.4).

Table 7.1

Errors

Code

Displayed

on LCD

Indication of DEVICE_

STATUS_#

Cause

Remedy

- - -

YTA does not participate in the

network.

Check the communication related

parameters. See A.5.2 for details.

The AI block to be displayed on

the LCD is not yet scheduled.

Check the setting of DISPLAY_AI_OUT

in TB block.

AL001

No Response From AD

Board

Failure in input circuitry of

hardware

Make a service call.

AL003

EEPROM failure

EEPROM failure

Make a service call.

AL004

Flash ROM SUM Error

Flash ROM failure

Make a service call.

AL005

PPM Communication Error Internal communication error

Make a service call.

AL006

Parsley Receive Error

Internal communication error

Make a service call.

AL007

AMP Temp Counter Too

High

Hardware failure

Make a service call.

AL008

AMP Temp Counter Too

Low

Hardware failure

Make a service call.

AL010

WDT 3 Times Over Error

Hardware failure

Make a service call.

AL021

RB in O/S Mode

The actual mode of the resource

block is O/S.

Set the target mode of the resource block

to Auto.

AL022

TB in O/S Mode

The actual mode of the

transducer block is O/S.

Set the target mode of the transducer

block to Auto.

AL030

Start Backup Mode of

Channel6

The backup sensor input is

selected for channel 6.

Restore the sensor 1 input to normal.

Then, set 1 (Enable) in BACKUP_

RETURN_SENSOR1, or turn off the

power once and back on again.

AL031

Not Used Sensor1

Although a channel number

related to sensor 1 (see note)

is assigned to an AI or DI block,

SENSOR_TYPE_1 is set to Non-

connection.

Do not assign to any AI or DI block a

channel number related to sensor 1 (see

note) when the sensor 1 input is not

used. When using the sensor 1 input, set

SENSOR_TYPE_1 correctly.

Advertising