<Appendix 1. List of Parameters for Each Block of the YTA>

A1-3

IM 01C50T02-01E

Relative

Index

Index Parameter Name

Factory Default

Write

Mode

Explanation

36

1036 BLOCK_ALM

The block alarm is used for all configuration,

hardware, connection failure or system problems

in the block. The cause of the alert is entered in the

subcode field. The first alert to become active will

set the Active status in the Status attribute. As soon

as the Unreported status is cleared by the alert

reporting task, another block alert may be reported

without clearing the Active status, if the subcode

has changed.

37

1037 ALARM_SUM

Enable

The current alert status, unacknowledged states,

unreported states, and disabled states of the

alarms associated with the function block.

38

1038 ACK_OPTION

0xffff: unack

Auto

39

1039 WRITE_PRI

0

Auto

Priority of the alarm generated by clearing the write

lock.

40

1040 WRITE_ALM

This alert is generated if the write lock parameter is

cleared.

41

1041 ITK_VER

4

Version number of interoperability test by Fieldbus

Foundation applied to YTA.

42

1042 SOFT_REV

YTA software revision number.

43

1043 SOFT_DESC

Yokogawa internal use.

44

1044 SIM_ENABLE_MSG Null

Auto

Software switch for simulation function.

45

1045 DEVICE_STATUS_1 0

Device status (VCR setting etc.)

46

1046 DEVICE_STATUS_2 0

Device status (failure or setting error etc.)

47

1047 DEVICE_STATUS_3 0

Device status (failure or setting error etc.)

48

1048 DEVICE_STATUS_4 0

Device status

49

1049 DEVICE_STATUS_5 0

Device status

50

1050 DEVICE_STATUS_6 0

Device status

51

1051 DEVICE_STATUS_7 0

Device status

52

1052 DEVICE_STATUS_8 0

Device status

*1: FF-891 “Foundation

TM

Specification Function Block Application Process Part 2”

A1.2 Al Function Block

Relative

Index

Index

Parameter

Name

Factory

Default

Write

Mode

Explanation

AI1 AI2 AI3 AI4

0

4000 4100 4200 4300 Block Header TAG:“AI1”,

“AI2”,“AI3” or

“AI4”

Block Tag

= O/S

Information on this block such as Block

Tag, DD Revision, Execution Time etc. The

value for “Period of Execution” should be

larger than “Execution Time.”

1

4001 4101 4201 4301 ST_REV

The revision level of the static data

associated with the function block. The

revision value will be incremented each

time a static parameter value in the block is

changed.

2

4002 4102 4202 4302 TAG_DESC

(blank)

Auto

The user description of the intended

application of the block.

3

4003 4103 4203 4303 STRATEGY

1

Auto

The strategy field can be used to identify

grouping of blocks. This data is not

checked or processed by the block.

4

4004 4104 4204 4304 ALERT_KEY 1

Auto

The identification number of the plant unit.

This information may be used in the host

for sorting alarms, etc.

5

4005 4105 4205 4305 MODE_BLK AI1,AI2:Auto

AI3,AI4:O/S

Auto

The actual, target, permitted, and normal

modes of the block.

6

4006 4106 4206 4306 BLOCK_ERR —

This parameter reflects the error status

associated with the hardware or software

components associated with a block. It is

a bit string, so that multiple errors may be

shown.