<Appendix 1. List of Parameters for Each Block of the YTA>

A1-4

IM 01C50T02-01E

Relative

Index

Index

Parameter

Name

Factory

Default

Write

Mode

Explanation

AI1 AI2 AI3 AI4

7

4007 4107 4207 4307 PV

Either the primary analog value for use in

executing the function, or a process value

associated with it. May also be calculated

from the READBACK value of an AO block.

8

4008 4108 4208 4308 OUT

Value =

Man

The primary analog value calculated as a

result of executing the function.

9

4009 4109 4209 4309 SIMULATE

Disable

Auto

Allows the transducer analog input or

output to the block to be manually supplied

when simulate is enabled. When simulation

is disabled, the simulate value and status

track the actual value and status.

10

4010 4110 4210 4310 XD_SCALE

Specified at

the time of

order

O/S

The high and low scale values, engineering

units code, and number of digits to the right

of the decimal point used with the value

obtained from the transducer for a specified

channel. Refer to Table A1.5 for the unit

available.

11

4011 4111 4211 4311 OUT_SCALE 0 - 100 %

O/S

The high and low scale values, engineering

units code, and number of digits to the right

of the decimal point to be used in displaying

the OUT parameter and parameters which

have the same scaling as OUT.

12

4012 4112 4212 4312 GRANT_

DENY

0

Auto

Options for controlling access of host

computers and local control panels to

operating, tuning and alarm parameters of

the block.

13

4013 4113 4213 4313 IO_OPTS

0

O/S

Options which the user may select to alter

input and output block processing.

14

4014 4114 4214 4314 STATUS_

OPTS

0

O/S

Options which the user may select in the

block processing of status.

15

4015 4115 4215 4315 CHANNEL

AI1: 1

AI2: 2

AI3,AI4: 3

O/S

The number of the logical hardware

channel that is connected to this I/O block.

This information defines the transducer to

be used going to or from the physical world.

16

4016 4116 4216 4316 L_TYPE

Specified at

the time of

order

Man

Determines if the values passed by the

transducer block to the AI block may be

used directly (Direct) or if the value is in

different units and must be converted

linearly (Indirect), or with square root (Ind

Sqr Root), using the input range defined by

the transducer and the associated output

range.

17

4017 4117 4217 4317 LOW_CUT

0%

Auto

Limit used in square root processing. A

value of zero percent of scale is used in

block processing if the transducer value

falls below this limit, in % of scale. This

feature may be used to eliminate noise

near zero for a flow sensor.

18

4018 4118 4218 4318 PV_FTIME

0sec

Auto

Time constant of a single exponential filter

for the PV, in seconds.

19

4019 4119 4219 4319 FIELD_VAL

Raw value of the field device in percent

of thePV range, with a status reflecting

the Transducer condition, before signal

characterization (L_TYPE) or filtering

(PV_FTIME).

20

4020 4120 4220 4320 UPDATE_

EVT

This alert is generated by any change to

the static data.