<9. General Specifications>

9-1

IM 01C50T02-01E

9. General Specifications

9.1 Standard Specifications

For items other than those described below,

refer to IM 01C50B01-01E.

Applicable Model:

YTA320

Accuracy

See Table 9.1 in Page 9-4.

Ambient Temperature Effect per 10°C Change

See Table 9.2 in Page 9-5.

Output Signal:

Digital communication signal based on

FOUNDATION Fieldbus protocol.

Supply Voltage:

9 to 32 V DC for general use and flameproof

type

9 to 24 V DC for intrinsically safe type Entity

model

9 to 17.5 V DC for intrinsically safe type FISCO

model

Conditions of Communication Line:

Supply Voltage: 9 to 32 V DC

Supply Current: 16.6 mA (max)

Functional Specifications:

Functional specifications for Fieldbus

communication conform to the standard

specifications (H1) of

FOUNDATION Fieldbus.

Function Block:

Four AI function blocks

Four DI function blocks

One/Two PID function blocks (option)

Link Master funtion

< Settings When Shipped >

Sensor type

‘Pt100, 3 wire system’ (for both inputs), or as specified in

order.

Tag Number (PD tag)

‘TT1001’ unless otherwise specified in order. (Not

engraved on tag plate in such case.) *

1

Output Mode (L_TYPE)

‘Indirect’ unless otherwise specified in order

Calibration Range (XD_SCALE) Lower/Higher Range Value ‘0 to 100’, or as specified in order
Unit of Calibration Range

Selected from °C and Kelvin. (Only one unit can be

specified.) When optional code /D2 is specified, °F and °R

can also be specified.

Output Scale (OUT_SCALE) Lower/Higher Range Value

‘0 to 100%’

Damping Time Constant (PV_FTIME of TB)

‘2 sec.’

Node Address (in hexadecimal)

‘0 × F3’ unless otherwise specified in order

BOOT_OPERAT_FUNCTION_CLASS

‘BASIC’ unless otherwise specified in order