<Appendix 4. PID Block>

A4-10

IM 01C50T02-01E

A4.19 Example of Block

Connections

PID

BKCAL_IN

OUT

IN

AO

BKCAL_OUT

CAS_IN

AI

OUT

FA0406.ai

When configuring a simple PID control loop by

combining a YTA transmitter with a fieldbus valve

positioner that contains an AO block, follow the

procedure below to make the settings of the

corresponding fieldbus function blocks:

1. Connect the AI block and PID block of the YTA,

and the AO block of the valve positioner as

shown above.

2. Set MODE_BLK.target of the PID block to

O/S, and then set GAIN, RESET, and RATE to

appropriate values.

3. Check that the value of MODE_BLK.actual of

the AI block is Auto.

4. Set MODE_BLK.target of the AO block to

CAS|AUTO (meaning "Cas and Auto").

5. Check that the value of BKCAL_IN.status of the

PID block is not Bad.

6. Check that the value of IN.status of the PID

block is not Bad.

7. Check that Auto is set in MODE_BLK.permitted

of the PID block.

8. Set MODE_BLK.target of the PID block to Auto.


When finishing all steps in order, the PID block and

AO block exchange the respective information and

initialize the cascade connection. Consequently,

the value of MODE_BLK.actual of the PID block

changes to Auto and automatic PID control starts.

A4.19.1 View Object for PID Function Block

Relative

Index

Parameter

Mnemonic

VIEW

1

VIEW

2

VIEW

3

VIEW

4

1

ST_REV

2

2

2

2

2

TAG_DESC

3

STRATEGY

2

4

ALERT_KEY

1

5

MODE_BLK

4

4

6

BLOCK_ERR

2

2

7

PV

5

5

8

SP

5

5

9

OUT

5

5

10

PV_SCALE

11

11

OUT_SCALE

11

12

GRANT_DENY

2

13

CONTROL_OPTS

2

14

STATUS_OPTS

2

15

IN

5

16

PV_FTIME

4

17

BYPASS

1

18

CAS_IN

5

5

19

SP_RATE_DN

4

20

SP_RATE_UP

4

21

SP_HI_LIM

4

22

SP_LO_LIM

4

23

GAIN

4

24

RESET

4

25

BAL_TIME

4

26

RATE

4

27

BKCAL_IN

5

28

OUT_HI_LIM

4

29

OUT_LO_LIM

4

30

BKCAL_HYS

4

31

BKCAL_OUT

5

32

RCAS_IN

5

33

ROUT_IN

5

Subtotals

28

43

53

41

Advertising
This manual is related to the following products: