4 parameters of transducer block, Parameters of transducer block -12, Important – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 25

Advertising
background image

<5. Configuration>

5-12

IM 01C50T02-01E

5.6.4 Parameters of Transducer Block

The transducer block makes settings for the

temperature transmitter-specific functions of the

YTA320, such as the temperature input and display

settings. See Appendix 1 for a list of all parameters

of the YTA320; this section describes only the

settings for important parameters.
Note that you can choose “˚C” or “Kelvin” as the unit

of temperature. “˚F” or “˚R” can also be selected for

a model with the option code /D2.

Mode Setting Parameter

MODE_BLK

Supports O/S and Auto modes. In the O/S

mode, the transducer block does not function,

as implied by the mode name “Out of Service.”

Parameters Related to Sensor Input

The number “2” enclosed in parentheses

appearing in the following parameter names

and descriptions indicates that the preceding

number “1” should be read as “2” for the cases

of sensor 2, respectively.

SENSOR_TYPE_1 (2)

Shows and stipulates the type of sensor

connected to sensor input 1 (or 2). The

following sensors can be connected.

· Thermocouple:

Types B, E, J, K, N, R, S, and T (IEC584),

types L and U (DIN43710), and Types W3

and W5 (ASTM E-988)

· 2-/3-/4-wire RTD:

Pt100, Pt200, Pt500 (IEC751) JPt100

(JIS), Ni120, Cu (SAMARC21-4)

· 2-/3-/4-wire resistance input

· 2-wire DC mV input

IMPORTANT

Whenever 4-wire input is specified for Sensor 1,

set ‘Non Connection’ for Sensor 2.

4-wire input cannot be used as Sensor 2.

SENSOR_CONNECTION_1 (2)

Shows and stipulates the number of wires

connected to sensor input 1 (or 2). This setting

only valid for RTD and resistance input.

PRIMARY_VALUE_1 (2)

Shows the value and status of the input from

sensor 1 (or 2). The unit set in PRIMARY_

VALUE_RANGE_1 (or ..._2) applies to the unit

of the value. The damping time constant is set

in PRIMARY_VALUE_FTIME_1 (or ..._2).

NOTE

If an input exceeds the range shown in PRIMAR

Y_VALUE_RANGE_1(2), the value up to 120%

of the range will be output for upper limit side,

and -20% of the range will be output for lower

limit side. In thie case, the accuracy of the input

exceeding the range shall not be guaranteed.

SECONDARY_VALU

Shows the value and status of the terminal

board temperature. The unit of temperature

is set in SECONDARY_VALUE_UNIT, and

the damping time constant in SECONDARY_

VALUE_FTIME.

DIFFERENTIAL_VALUE

Shows the value and status of the difference

between 2 inputs [sensor 1 input value minus

sensor 2 input value] when 2 sensors are

connected. The unit of temperature is set in

DIFFERENTIAL_UNIT, and the damping time

constant in DIFFERENTIAL_VALUE_FTIME.

When there is no connection to sensor 2 input,

the status of DIFFERENTIAL_VALUE is Bad

and the value is undefined.

AVERAGE_VALUE

Shows the value and status of the average of

2 inputs when 2 sensors are connected. The

unit of temperature is set in AVERAGE_UNIT,

and the damping time constant in AVERAGE_

VALUE_FTIME. When there is no connection

to sensor 2 input, the status of AVERAGE_

VALUE is Bad and the value is undefined.

BACKUP_VALUE

When 2 sensors are connected, this parameter

normally shows the value input from sensor

1, and in case of burnout of sensor 1 (when

the backup action becomes active), shows

the value input from sensor 2. The unit and

damping time constant follow the respective

settings for the input currently selected.

Advertising
This manual is related to the following products: