<8. Handling Caution>

8-8

IM 01C50T02-01E

IFM018-A12

Installation Diagram

(Intrinsically safe, Division 1 Installation)

Non Hazardous Location

Hazardous Location

F0807.ai

Terminator

Transmitter

Safety Barrier

Temperature

Transmitter

Terminator

Transmitter

1

2

3

4

5

SUPPLY

SENSOR

*1:

Dust-tight conduit seal must be used when installed in

Class II and Class III environments.

*2:

Control equipment connected to the Associated Apparatus

must not use or generate more than 250 Vrms or Vdc.

*3:

Installation should be in accordance with ANSI/ISA

RP12/6 “Installation of Intrinsically Safe Systems for

Hazardous (Classified) Locations” and the National

Electrical Code (ANSI/NFPA 70) Sections 504 and 505.

*4:

The configuration of Associated Apparatus must be

Factory Mutual Research Approved under FISCO

Concept.

*5:

Associated Apparatus manufacturer’s installation drawing

must be followed when installing this equipment.

*6:

The YTA Series are approved for Class I, Zone 0,

applications. If connecting AEx (ib) associated Apparatus

or AEx ib I.S. Apparatus to the Zone 2, and is not suitable

for Class I, Zone 0 or Class I, Division 1, Hazardous

(Classified) Locations.

*7:

No revision to drawing without prior Factory Mutual

Research Approval.

*8:

Terminator must be FM Approved.

Electrical Data:
• Rating 1 (Entity and nonincendive)

For Groups A, B, C, D, E, F, and G or Group IIC

Maximum Input Voltage Vmax: 24 V

Maximum Input Current Imax: 250 mA

Maximum Input Power Pi: 1.2 W

Maximum Internal Capacitance Ci: 1.5 nF

Maximum Internal Inductance Li: 8 µH

or

• Rating 2 (FISCO)

For Groups A, B, C, D, E, F, and G or Group IIC

Maximum Input Voltage Vmax: 17.5 V

Maximum Input Current Imax: 360 mA

Maximum Input Power Pi: 2.52 W

Maximum Internal Capacitance Ci: 1.5 nF

Maximum Internal Inductance Li: 8 µH

or

• Rating 3 (FISCO)

For Groups C, D, E, F, and G or Group IIB

Maximum Input Voltage Vmax: 17.5 V

Maximum Input Current Imax: 380 mA

Maximum Input Power Pi: 5.32 W

Maximum Internal Capacitance Ci: 1.5 nF

Maximum Internal Inductance Li: 8 µH

and

• Rating 4 (Sensor circuit)

Maximum Output Voltage Uo: 6.7 V

Maximum Output Current Io: 60 mA

Maximum Output Power Po: 100 mW

Maximum External Capacitance Co: 10 µF

Maximum External Inductance Lo: 10 µH

Note: In the rating 1, the output current of the barrier must be

limited by a resistor “Ra” such that Io=Uo/Ra. In the rating

2 or 3, the output characteristics of the barrier must be the

type of trapezoid which are certified as the FISCO model

(See “FISCO Rules”). The safety barrier may include

a terminator. More than one field instruments may be

connected to the power supply line.

FISCO Rules

The FISCO Concept allows the interconnection

of intrinsincally safe apparatus to associated

apparatus not specifically examined in such

combination. The criterion for such interconnection

is that the voltage (Ui), the current (Ii) and the power

(Pi) which intrinsically safe apparatus can receive

and remain intrinsically safe, considering faults,

must be equal or greater than the voltage (Uo, Voc,

Vt), the current (Io) and the power (Po) which can

be provided by the associated apparatus (supply

unit). In addition, the maximum unprotected residual

capacitance (Ci) and inductance (Li) of each

apparatus (other than the terminators) connected to

the fieldbus must be less than or equal to 5 nF and

10 µH respectively.

In each I.S. fieldbus segment only one active

source, normally the associated apparatus, is

allowed to provide the necessary power for the

fieldbus system.