<Appendix 1. List of Parameters for Each Block of the YTA>

A1-8

IM 01C50T02-01E

Relative

Index

Index

Parameter Name

Default

(factory setting)

Write

Description

13

2013 PRIMARY_VALUE

_TYPE_1

104

Auto

Defines the type of primary value 1 (sensor 1

input). The following can be chosen for a YTA

transmitter:

104 = Process temperature

105 = Non process temperature

112 = mV

200 = ohm

14

2014 PRIMARY_VALUE

_1

Stores the value of the sensor 1 input.

15

2015 PRIMARY_VALUE

_RANGE_1

Sensor range

Defines the upper and lower range limits

and unit of PRIMARY_VALUE_1; differs

depending on the sensor selected.

16

2016 CAL_POINT_HI_1

O/S

Upper value for calibrations of sensor 1 input.

17

2017 CAL_POINT_LO_1 —

O/S

Lower value for calibrations of sensor 1 input.

18

2018 CAL_MIN_SPAN_1 Minimum span

Minimum calibration span for sensor 1 input.

19

2019 CAL_UNIT_1

mV or ohm

Unit of calibration value for sensor 1. Set to

"mV" for a thermocouple or mV input, or to

"ohm" for an RTD or resistance input.

20

2020 SENSOR_TYPE_1 As specified by the

customer before

shipment

O/S

Type of sensor 1.

21

2021 SENSOR_RANGE_

1

Range of sensor

Range of sensor 1.

22

2022 SENSOR_SN_1

O/S

Serial number of sensor 1.

23

2023 SENSOR_CAL

_METHOD_1

103

Auto

Calibration method for sensor 1:

103 = Factory trim standard calibration

104 = User trim standard calibration

24

2024 SENSOR_CAL_

LOC _1

Auto

Shows and is used to record the location

where sensor 1 was calibrated.

25

2025 SENSOR_CAL

_DATE_1

Auto

Shows and is used to record the date when

sensor 1 was calibrated.

26

2026 SENSOR_CAL

_WHO_1

Auto

Shows and is used to record the person who

calibrated sensor 1.

27

2027 SENSOR _

CONNECTION_1

As specified by the

customer before

shipment

O/S

Number of connection wires of sensor 1.

28

2028 PRIMARY_VALUE

_TYPE_2

104

Auto

Defines the type of primary value 2 (sensor 2

input). The following can be chosen for a YTA

transmitter:

104 = Process temperature

105 = Non process temperature

112 = mV

200 = ohm

29

2029 PRIMARY_VALUE_

2

Stores the value of the sensor 2 input.

30

2030 PRIMARY_VALUE_

RANGE_2

Sensor range

Defines the upper and lower range limits

and unit of PRIMARY_VALUE_2; differs

depending on the sensor selected.

31

2031 CAL_POINT_HI_2

O/S

Upper value for calibrations of the sensor 2

input.

32

2032 CAL_POINT_LO_2 —

O/S

Lower value for calibrations of the sensor 2

input.

33

2033 CAL_MIN_SPAN_2 Minimum span

Minimum calibration span for the sensor 2

input.

34

2034 CAL_UNIT_2

mV or ohm

Unit of calibration value for sensor 2. Set to

"mV" for a thermocouple or mV input, or to

"ohm" for an RTD or resistance input.

35

2035 SENSOR_TYPE_2 As specified by the

customer before

shipment

O/S

Type of sensor 2.