Appendix 4. pid block, A4.1 function diagram, A4.2 functions of pid block – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 77: A4.1, A4.2, A4-1

Advertising
background image

<Appendix 4. PID Block>

A4-1

IM 01C50T02-01E

Appendix 4. PID Block

A PID block performs the PID control computation based on the deviation of the measured value (PV) from the

setpoint (SV), and is generally used for constant-setpoint and cascaded-setpoint control.

A4.1 Function Diagram

The figure below depicts the function diagram of a PID block.

Setpoint

Output

Bypass

Input Filter

PID Control

Computation

Alarm

Processing

Mode Control

Feed-forward

Data Status

Management

Output Tracking

CAS_IN

BKCAL_OUT
RCAS_OUT

BKCAL_IN

ROUT_IN

ROUT_OUT

FF_VAL

RCAS_IN

TRK_IN_D

TRK_VAL

IN

OUT

PV

SP

FA0401.ai

A4.2 Functions of PID Block

The table below shows the functions provided in a PID block.

Function

Description

PID control computation

Computes the control output in accordance with the PID control algorithm.

Control output

Converts the change in control output ∆MV to the manipulated value MV that is to be actually

output.

Switching of direction of

control action

Switches over the direction of control action between direct and reverse, i.e., the direction of

changes in the control output depending on the changes in the deviation.

Control action bypass

When the bypass is on, the value of the SP is scaled to the range of the OUT and output as

the OUT.

Feed-forward

Adds the value of the FF_VAL (input to the PID block) to the output from the PID computation.

Measured-value tracking Equalizes the setpoint SP to the measured value PV.
Setpoint limiters

Limit the value of setpoint SP within the preset upper and lower levels as well as limit the rate

of change when the PID block is in Auto mode.

External-output tracking

Performs the scaling of the value of TRK_VAL to the range of the OUT and outputs it as the

OUT.

Mode change

Changes the block mode between 8 modes: O/S, IMan, LO, Man, Auto, Cas, RCas, ROut.

Bumpless transfer

Prevents a sudden change in the control output OUT at changes in block mode and at

switching of the connection from the control output OUT to the cascaded secondary function

block.

Initialization and manual

fallback

Changes the block mode to IMan and suspends the control action when the specified

condition is met.

Manual fallback

Changes the block mode to Man and aborts the control action.

Auto fallback

Changes the block mode to Auto when it is Cas, and continues the control action with the

setpoint set by the operator.

Mode shedding upon

computer failure

Changes the block mode in accordance with the SHED_OPT setting upon a computer failure.

Alarm processing

Generates block alarms and process alarms, and performs event updates.

Advertising
This manual is related to the following products: