<Appendix 1. List of Parameters for Each Block of the YTA>

A1-10

IM 01C50T02-01E

Relative

Index

Index

Parameter Name

Default

(factory setting)

Write

Description

58

2058 SENSOR_MATCH

_BETA_1

0

O/S

Value of the factor ß used in the sensor

matching function for the sensor 1 input

59

2059 PRIMARY_VALUE

_FTIME_2

2 second

O/S

Time constant (in seconds) of the first-order

lag filter applied to the sensor 2 input

60

2060 CAL_STATE_2

0 (User Cal Off)

O/S

Indicates the validity of user calibration for

sensor 2:

0 =User Cal Off(Invalidate user-set

calibration values)

1 = User Cal On(Validate user-set calibration

values)

2 = Calibration Exec(User calibration mode)

61

2061 CJC_SELECT_2

0 (internal CJC)

O/S

Selects whether the terminal board

temperature or user-set constant

(CONSTANT_CJC_TEMP_2) is to be used

for cold junction compensation (CJC) for the

sensor 2 input. Valid for Thermocouple input

only.

0=Internal CJC

1=Constant CJC

62

2062 CONSTANT_CJC

_TEMP_2

0

O/S

User-set constant for CJC for the sensor 2

input. Setting 0 in this parameter disables

RJC. Valid only when CJC_SELECT_2 is set

to 1.

63

2063 WIRING _

RESISTANCE_2

0

O/S

Wiring resistance of the sensor 2 input. For a

2-wire resistance input, the input resistance

minus this value is used as the temperature

value.

64

2064 SENSOR_MATCH

_R0_2

O/S

Value of the factor R0 used in the sensor

matching function for the sensor 2 input

65

2065 SENSOR_MATCH

_A_2

O/S

Value of the factor A used in the sensor

matching function for the sensor 2 input

66

2066 SENSOR_MATCH

_B_2

O/S

Value of the factor B used in the sensor

matching function for the sensor 2 input

67

2067 SENSOR_MATCH

_C_2

O/S

Value of the factor C used in the sensor

matching function for the sensor 2 input

68

2068 SENSOR_MATCH

_ALPHA_2

O/S

Value of the factor α used in the sensor

matching function for the sensor 2 input

69

2069 SENSOR_MATCH

_DELTA_2

O/S

Value of the factor δ used in the sensor

matching function for the sensor 2 input

70

2070 SENSOR_MATCH

_BETA_2

O/S

Value of the factor ß used in the sensor

matching function for the sensor 2 input

71

2071 SECONDARY

_VALUE_FTIME

0

O/S

Time constant (in seconds) of the first-

order lag filter applied to the terminal board

temperature input. (0 to 99)

72

2072 DIFFERENTIAL

_VALUE

Indicates the difference between the two

inputs.

73

2073 DIFFERENTIAL

_UNIT

°C

Auto

Unit of the value of DIFFERENTIAL_VALUE

74

2074 DIFFERENTIAL

_VALUE_FTIME

2 second

O/S

Time constant (in seconds) of the first-order

lag filter applied to DIFFERENTIAL_VALUE

(0 to 99)

75

2075 AVERAGE_VALUE —

Indicates the average of the two inputs.

76

2076 AVERAGE_UNIT

°C

Auto

Unit of the value of AVERAGE_VALUE

77

2077 AVERAGE_VALUE

_FTIME

2 second

O/S

Time constant (in seconds) of the first-order

lag filter applied to AVERAGE_VALUE (0 to

99)

78

2078 BACKUP_VALUE

Indicates the value of the sensor 1 input

normally, and the value of sensor 2 in case of

burnout of sensor 1.

79

2079 BACKUP_UNIT

°C

Auto

Unit of the value of BACKUP_VALUE