3 definition of combining function blocks, Definition of combining function blocks -3 – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 16

Advertising
background image

<5. Configuration>

5-3

IM 01C50T02-01E

5.3 Definition of Combining

Function Blocks

The input/output parameters for function blocks

are combined. For the YTA, four AI blocks output

parameter (OUT), four DI blocks output parameter

(OUT_D) and PID block are subject to combination.

They are combined with the input of the control

block as necessary. Practically, setting is written to

the YTA link object with reference to “Block setting”

in Section 5.6 for details. It is also possible to read

values from the host at proper intervals instead of

connecting the YTA block output to other blocks.
The combined blocks need to be executed

synchronously with other blocks on the

communications schedule. In this case, change

the YTA schedule according to the following table.

Enclosed values in the table are factory-settings.

Table 5.3

Execution Schedule of the YTA

Function Blocks

Index

Parameters

Setting (Enclosed is

factory-setting)

269

(SM)

MACROCYCLE_

DURATION

Cycle (MACROCYCLE)

period of control or

measurement. Unit is

1/32 ms. (16000 = 0.5 s)

276

(SM)

FB_START_ENTRY.1 AI1 block startup time.

Elapsed time from the

start of MACROCYCLE

specified in 1/32 ms.

(0 = 0 s)

277

(SM)

FB_START_ENTRY.2 AI2 block startup time.

Elapsed time from the

start of MACROCYCLE

specified in 1/32 ms.

(4000 = 125 ms)

278

to

285

(SM)

FB_START_ENTRY.3

to

FB_START_ENTRY.10

Not used.

A maximum of 50 ms is taken for execution of each

AI block. A maximum of 30 ms is taken for execution

of each DI block, and 100ms for each PID block.

For scheduling of communications for combination

with the next function block, the execution is so

arranged as to start after a lapse of longer than 100

ms. In no case should function blocks of the YTA

be executed at the same time (execution time is

overlapped).
Figure 5.3 shows an example of schedule based on

the loop shown in Figure 5.2.

F0502.ai

TIC100

TC200

TV200

TT 200

YTA

#2

TT100

YTA

#1

Figure 5.2

Example of Loop Connecting

Function Block of Two YTA with Other

Instruments

TT100

TIC100

TC200

TV200

TT200

Function

Block

Schedule

Commu-

nication

Schedule

OUT

IN

OUT

CAS_IN

BKCAL_OUT

BKCAL_IN

BKCAL_IN

BKCAL_OUT

IN

Unscheduled

Communication

Scheduled

Communication

F0503.ai

Macrocycle (Control Period)

Figure 5.3

Function Block Schedule and

Communication Schedule

When the control period (macrocycle) is set to more

than 4 seconds, set the following interval to be more

than 1% of the control period.

- Interval between “end of block execution” and

“start of sending CD from LAS”

- Interval between “end of block execution” and

“start of the next block execution”

Advertising