<Appendix 1. List of Parameters for Each Block of the YTA>

A1-11

IM 01C50T02-01E

Relative

Index

Index

Parameter Name

Default

(factory setting)

Write

Description

80

2080 BACKUP_

RETURN_

SENSOR1

0 (DISABLE)

O/S

Setting 1 in this parameter switches the value

to be output from the sensor 2 input back to

the sensor 1 input:

0 = DISABLE

1 = ENABLE

81

2081 SENSOR_

BURNOUT_

DETECT

0 (on)

O/S

Switches on and off the sensor burnout

detection:

0 = On

1 = Off

In most cases, this parameter should be set to

0(ON). If this is set to OFF, the sensor burnout

detecting function will not correctly work.

82

2082 LIMSW_1_VALUE_

D

Indicates the value and status of limit switch 1.

83

2083 LIMSW_1_TARGET 0

O/S

Value to be monitored by limit switch 1:

0 = PRIMARY_VALUE_1

1 = PRIMARY_VALUE_2

2 = SECONDARY_VALUE

3 = DIFFERENTIAL_VALUE

4 = AVERAGE_VALUE

5 = BACKUP_VALUE

84

2084 LIMSW_1

_SETPOINT

0

O/S

Threshold of switching on limit switch 1

85

2085 LIMSW_1_ACT

_DIRECTION

0 (high-limit switch) O/S

Type of limit switch 1:

0 = HI LIMIT (high-limit switch)

1 = LO LIMIT (low-limit switch)

86

2086 LIMSW_1

_HYSTERESIS

0

O/S

Hysteresis of limit switch 1. Input of only a

positive number is valid.

87

2087 LIMSW_1_UNIT

Unit of LIMSW_1_SETPOINT and LIMSW_1_

HYSTERESIS

88

2088 LIMSW_2_VALUE_

D

Indicates the value and status of limit switch 2.

89

2089 LIMSW_2_TARGET 0

O/S

Value to be monitored by limit switch 2. The

setting and the corresponding value are the

same as those for limit switch 1 (LIMSW_1_

TARGET).

90

2090 LIMSW_2

_SETPOINT

0

O/S

Threshold of switching on limit switch 2

91

2091 LIMSW_2_ACT_

DIRECTION

0 (high-limit switch) O/S

Type of limit switch 2. The setting and the

corresponding type are the same as those for

limit switch 1 (LIMSW_1_ACT_DIRECTION).

92

2092 LIMSW_2

_HYSTERESIS

0

O/S

Hysteresis of limit switch 2. Input of only a

positive number is valid.

93

2093 LIMSW_2_UNIT

Unit of LIMSW_2_SETPOINT and LIMSW_2_

HYSTERESIS

94

2094 LIMSW_3_VALUE_

D

Indicates the value and status of limit switch 3.

95

2095 LIMSW_3_TARGET 0

O/S

Value to be monitored by limit switch 3. The

setting and the corresponding value are the

same as those for limit switch 1 (LIMSW_1_

TARGET).

96

2096 LIMSW_3

_SETPOINT

0

O/S

Threshold of switching on limit switch 3

97

2097 LIMSW_3_ACT

_DIRECTION

0 (high-limit switch) O/S

Type of limit switch 3. The setting and the

corresponding type are the same as those for

limit switch 1 (LIMSW_1_ACT_DIRECTION).

98

2098 LIMSW_3

_HYSTERESIS

0

O/S

Hysteresis of limit switch 3. Input of only a

positive number is valid.

99

2099 LIMSW_3_UNIT

Unit of LIMSW_3_SETPOINT and LIMSW_3_

HYSTERESIS