<5. Configuration>

5-2

IM 01C50T02-01E

5.2 Network Definition

Before connection of devices with Fieldbus, define

the Fieldbus network. Allocate PD Tag and node

addresses to all devices (excluding such passive

devices as terminators).
The PD Tag is the same as the conventional

one used for the device. Up to 32 alphanumeric

characters may be used for definition. Use a

hyphen as a delimiter as required.
The node address is used to specify devices for

communication purposes. Because data is too long

for a PD Tag, the host uses the node address in

place of the PD Tag for communication. A range of

16 to 247 (or hexadecimal 10 to F7) can be set. The

device (LM device) with bus control function (Link

Master function) is allocated from a smaller address

number (16) side, and other devices (BASIC

device) without bus control function allocated from

a larger address number (247) side respectively.

Place YTA in the range of the BASIC device. When

the YTA is used as Link Master, place YTA in the

range of LM device. Set the range of addresses

to be used to the LM device. Set the following

parameters.

Table 5.1

Parameters for Setting Address Range

Symbol

Parameters

Description

V (FUN) First-Unpolled-

Node

Indicates the address

next to the address

range used for the host

or other LM device.

V (NUN) Number-of-

consecutive-

Unpolled-Node

Unused address range.

The devices within the address range written

as “Unused” in Figure 5.1 cannot be used on a

Fieldbus. For other address ranges, the range is

periodically checked to identify when a new device

is mounted. Care must be taken not to allow the

address range to become wider, which can lead to

exhaustive consumption of Fieldbus communication

performance.

Bridge device

Not used

0x10

0x00

0x14

0xF7

0xF8

0xFB

0xFC

0xFF

V(FUN)

V(FUN)+V(NUN)

LM device

Unused

V(NUN)

BASIC device

Default address

Portable device address

F0501.ai

Figure 5.1

Available Range of Node Addresses

To ensure stable operation of Fieldbus, determine

the operation parameters and set them to the LM

devices. While the parameters in Table 5.2 are to

be set, the worst-case value of all the devices to

be connected to the same Fieldbus must be used.

Refer to the specification of each device for details.

Table 5.2 lists YTA specification values.

Table 5.2

Operation Parameter Values of the YTA

to be Set to LM Devices

Symbol

Parameters

Description and

Settings

V (ST)

Slot-Time

Indicates the time

necessary for

immediate reply of thje

device. Unit of time is

in octets (256 μs). Set

maximum specification

for all devices. For

YTA, set a value of 4 or

greater.

V (MID)

Minimum-Inter-

PDU-Delay

Minimum value of

communication data

intervals. Unit of time

is in octets (256 μs).

Set the maximum

specification for all

devices. For YTA, set a

value of 4 or greater.

V (MRD) Maximum-Reply-

Delay

The worst case time

elapsed until a reply

is recorded. The

unit is Slot-time; set

the value so that V

(MRD) × V (ST) is the

maximum value of the

specification for all

devices. For YTA, the

setting must be a value

of 12 or greater.