A4.14 initialization and manual fallback (iman), A4.15 manual fallback, A4.16 auto fallback – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 84: A4-8

Advertising
background image

<Appendix 4. PID Block>

A4-8

IM 01C50T02-01E

A4.14 Initialization and Manual

Fallback (IMan)

Initialization and manual fallback denotes a set of

actions in which a PID block changes mode to IMan

(initialization and manual) and suspends the control

action. Initialization and manual fallback takes

place automatically as a means of abnormality

handling when the following condition is met:

• The quality component of BKCAL_IN.status is

Bad.

- OR -

• The quality component of BKCAL_IN.status is

Good (c)

- AND -

The sub-status component of BKCAL_IN.status

is FSA, LO, NI, or IR.

The user cannot manually change the mode to

IMan. A mode transition to IMan occurs only when

the condition above is met.

A4.15 Manual Fallback

Manual fallback denotes an action in which a

PID block changes mode to Man and suspends

the control action. Manual fallback takes place

automatically as a means of abnormality handling

when the following condition is met:

• IN.status is Bad except when the control action

bypass is on.

To enable the manual fallback action to take place

when the above condition is met, Target to Manual if

BAD IN must be specified beforehand in STATUS_

OPTS.
The table below shows the options in STATUS_

OPTS.

Options in

STATUS_

OPTS

Description

IFS if BAD IN Sets the sub-status component of

OUT.status to IFS if IN.status is Bad

except when PID control bypass is on.

IFS if BAD

CAS IN

Sets the sub-status component of

OUT.status to IFS if CAS_IN.status

is Bad.

Use

Uncertain as

Good

Does not regard

IN as being in Bad

status when

IN.status is Uncertain (to

prevent mode transitions from being

affected when it is Uncertain).

Target to

Manual if

BAD IN

Automatically changes the value of

MODE_BLK.target to MAN when IN

falls into Bad status.

Target to next

permitted

mode if BAD

CAS IN

Automatically changes the value of

MODE_BLK.target to Auto (or to Man

if Auto is not set in Permitted) when

CAS_IN falls into Bad status.

A4.16 Auto Fallback

Auto fallback denotes an action in which a PID

block changes mode from Cas to Auto and

continues automatic PID control with the user-set

setpoint. Auto fallback takes place automatically

when the following condition is met:

• IN.status (data status of IN) is Bad except when

the control action bypass is on.

To enable the manual fallback action to take place

when the above condition is met:

• Target to next permitted mode if BAD CAS

IN must be previously specified in STATUS_

OPTS.

- AND -
• Auto must be previously set in MODE_BLK.

permitted.