A4.11.2 when pid block is in cas or rcas mode, A4.12 external-output tracking, A4.13 measured-value tracking – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 83: A4-7

Advertising
background image

<Appendix 4. PID Block>

A4-7

IM 01C50T02-01E

Setpoint Rate Limits
The setpoint rate limits are used to restrict the

magnitude of changes in the SP value so as to

change the SP value gradually towards a new

setpoint.

• An increase of the SP value at each execution

period (period of execution in the Block Header)

is limited to the value of SP_RATE_UP.

• A decrease of the SP value at each execution

period (period of execution in the Block Header)

is limited to the value of SP_RATE_DOWN.

A4.11.2 When PID Block Is in Cas or RCas

Mode

By selecting Obey SP Limits if Cas or RCas in

CONTROL_OPTS (see Section A4.13), the setpoint

high/low limits can be put into force also when the

value of MODE_BLK is Cas or RCas.

A4.12 External-output Tracking

External tracking is an action of outputting the value

of the remote output TRK_VAL set from outside

the PID block, as illustrated in the figure below.

External tracking is performed when the block

mode is LO.

TRK_SCALE

OUT_SCALE

TRK_VAL

OUT

TRK_IN_D

LO mode

PID control

computation result

FA0404.ai

To change the block mode to LO:
(1) Select Track Enable in CONTROL_OPTS.

(2) Set TRK_IN_D to true.
However, to change the block mode from Man

to LO, Track in Manual must also be specified in

CONTROL_OPTS.

A4.13 Measured-value Tracking

Measured-value tracking, also referred to as SP-PV

tracking, is an action to equalize the setpoint SP

to the measured value PV when the block mode

(MODE_BLK.actual) is Man in order to prevent a

sudden change in control output from being caused

by a mode change to Auto.
While a cascade primary control block is performing

the automatic or cascade control (in the Auto or

Cas mode), when the mode of its secondary control

block is changed from Cas to Auto, the cascade

connection is opened and the control action of the

primary block stops. The SP of the secondary

controller can be equalized to its cascade input

signal CAS_IN also in this case.
The settings for measured-value tracking are made

in the parameter CONTROL_OPTS, as shown in

the table below.

Options in

CONTROL_

OPTS

Description

Bypass

Enable

This parameter allows BYPASS to be

set.

SP-PV

Track in

Man

Equalizes SP to PV when

MODE_BLK.

target is set to Man.

SP-PV

Track in

ROut

Equalizes SP to PV when

MODE_BLK.

target is set to ROut.

SP-PV

Track in LO

or IMan

Equalizes SP to PV when actual is set to

LO or IMAN.

SP-PV

Track

retained

Target

Equalizes SP to RCAS_IN when

MODE_

BLK.target is set to RCas, and to

CAS_IN when

MODE_BLK.target is set

to Cas when the actual mode of the block

is IMan, LO, Man or ROut.

Direct Acting Set the PID block to a direct acting

controller.

Track

Enable

This enables the external tracking

function. The value in TRK_VAL will

replace the value of OUT if TRK_IN_D

becomes true and the target mode is not

Man.

Track in

Manual

This enables TRK_VAL to replace the

value of OUT when the target mode is

Man and TRK_IN_D is true. The actual

mode will then be LO.

Use PV for

BKCAL_

OUT

Sets the value of PV in BKCAL_OUT and

RCAS_OUT, instead of the value of SP.

Obey SP

limits if Cas

or RCas

Puts the setpoint high/low limits in force

in the Cas or RCas mode.

No OUT

limits in

Manual

Disables the high/low limits for OUT in

the Man mode.