<4. Getting Started>

4-2

IM 01C50T02-01E

4.2 Host Setting

To activate Fieldbus, the following settings are

required for the host.

IMPORTANT

Do not turn off the power immediately after

setting. When the parameters are saved to

EEPROM, the redundant processing is executed

for the improvement of reliability. If the power

is turned off within 60 seconds after setting is

made, the modified parameters are not saved

and the settings may return to the original values.

Table 4.1

Operation Parameters

Symbol

Parameter

Description and

Settings

V (ST)

Slot-Time

Set 4 or greater value.

V (MID)

Minimum-Inter-

PDU-Delay

Set 4 or greater value.

V (MRD) Maximum-

Response-Delay

Set so that V (MRD) ×

V (ST) is 12 or greater

V (FUN) First-Unpolled-

Node

Indicate the address

next to the address

range used by the host.

Set 0x15 or greater.

V (NUN) Number-of-

consecutive-

Unpolled-Node

Unused address range.

YTA address is factory-

set to 0xF3. Set this

address to be within

the range of the BASIC

device in Figure 4.2.

Bridge device

Not used

0x10

0x00

0x14

0xF7

0xF8

0xFB

0xFC

0xFF

V(FUN)

V(FUN)+V(NUN)

YTA(0xF3)

LM device

Unused

V(NUN)

BASIC device

Default address

Portable device address

F0402.ai

Note 1: LM device: with bus control function (Link Master

function)

Note 2: BASIC device: without bus control function

Figure 4.2

Available Address Range

4.3 Bus Power ON

Turn on the power of the host and the bus. Where

the YTA is equipped with an LCD indicator, first all

segments are lit, then the display begins to operate.

If the indicator is not lit, check the polarity of the

power supply.
Using the host device display function, check that

the YTA is in operation on the bus.
The device information, including PD tag, Node

address, and Device ID, is described on the

sheet attached to YTA. The duplicates of device

information are provided on this sheet.

DEVICE INFORMATION

Device ID

:

5945430005XXXXXXXX

PD Tag

:

TT1001

Device Revision

:

X

Node Address

:

0xf3

Serial No.

:

XXXXXXXXXXXXXXXXX

Physical Location :

Note:

Our Device Description Files and Capabilities Files available at

http://www.yokogawa.com/fld/ (English) or
http://www.yokogawa.co.jp/fld/ (Japanese)

DEVICE INFORMATION

Device ID

:

5945430005XXXXXXXX

PD Tag

:

TT1001

Device Revision

:

X

Node Address

:

0xf3

Serial No.

:

XXXXXXXXXXXXXXXXX

Physical Location :

Note:

Our Device Description Files and Capabilities Files available at

http://www.yokogawa.com/fld/ (English) or
http://www.yokogawa.co.jp/fld/ (Japanese)

F0403.ai

Figure 4.3

Device Information Sheet Attached to

YTA

If no YTA is detected, check the available address

range and the polarity of the power supply. If the

node address and PD tag are not specified when

ordering, default value is factory set. If two or more

YTAs are connected at a time with default value,

one YTA will keep the address upon shipment while

the other will have a default address as they have

the same initial addres. Separately connect each

YTA and set a different address for each.