3 simulation function, 4 operation of integral indicator, Simulation function -2 – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 30: Operation of integral indicator -2

Advertising
background image

<6. In-process Operation>

6-2

IM 01C50T02-01E

Table 6.1

Alert Object

Subindex

Parameter

Name

Explanation

A

na

lo

g

A

le

rt

D

is

cr

et

e

A

le

rt

U

pd

at

e

A

le

rt

1

1

1

Block

Index

Index of block from

which alert is generated

2

2

2

Alert Key

Alert Key copied from

the block

3

3

3

Standard

Type

Type of the alert

4

4

4

Mfr Type

Alert Name identified by

manufacturer specific

DD

5

5

5

Message

Type

Reason of alert

notification

6

6

6

Priority

Priority of the alarm

7

7

7

Time

Stamp

Time when this alert is

first detected

8

8

Subcode

Enumerated cause of

this alert

9

9

Value

Value of referenced data

10

10

Relative

Index

Relative index of

referenced data

8

Static

Revision

Value of static revision

(ST_REV) of the block

11

11

9

Unit Index Unit code of referenced

data

6.3 Simulation Function

The simulation function simulates the input of a

function block and lets it operate as if the data was

received from the transducer block. It is possible to

conduct testing for the downstream function blocks

or alarm processes.
A SIMULATE_ENABLE switch is mounted in the

YTA amplifier. This is to prevent the accidental

operation of this function. When this is switched

on, simulation is enabled. (See Figure 6.2.) To

initiate the same action from a remote terminal,

if REMOTE LOOP TEST SWITCH (Note: in

capital letter) is written to the SIM_ENABLE_MSG

parameter (index 1044) of the resource block, the

resulting action is the same as is taken when the

above switch is on. Note that this parameter value

is lost when the power is turned OFF. In simulation

enabled status, an alarm is generated from the

resource block, and other device alarms will be

masked; for this reason the simulation must be

disabled immediately after using this function.
The SIMULATE parameter of AI block consists of

the elements listed in Table 6.2 below.

Table 6.2

SIMULATE(_D) Parameter

Subindex Parameters

Description

1

Simulate

Status

Sets the data status to be

simulated.

2

Simulate

Value

Sets the value of the data

to be simulated.

3

Transducer

Status

Displays the data status

from the transducer block.

It cannot be changed.

4

Transducer

Value

Displays the data value

from the transducer block.

It cannot be changed.

5

Simulate

En/Disable

Controls the simulation

function of this block.

1: Simulation disabled

(standard)

2: Simulation started

When Simulate En/Disable in Table 6.2 above is

set to 2, the applicable function block uses the

simulation value set in this parameter instead of

the data from the transducer block. This setting can

be used for propagation of the status to the trailing

blocks, generation of a process alarm, and as an

operation test for trailing blocks.

F0602.ai

1
2

O

N

"OFF" during operation

Not in use

SIM. ENABLE

Figure 6.2

SIMULATE_ENABLE Switch Position

6.4 Operation of Integral

Indicator

If integral indicator is specified, the LCD display

which can diplay output value of each AI block,

address and error codes is installed with the

instrument. Items to be displayed can be selected

in Transducer block parameters. (Refer to section

5.6.4.)

NOTE

Though the DISPLAY_WARNING parameter

is set to "SHOW", code for warning will not

be shown if the warning function is disabled

by parameters WARNING_ENABLE _# in

Transducer block.