<5. Configuration>

5-13

IM 01C50T02-01E

If you want to switch back to select sensor 1

input while the backup action is active after

the sensor 1 input recovers, set 1 (Enable) in

BACKUP_RETURN_SENSOR1. Because

this data is not retained, set 1(Enable) in the

parameter every switch back.

When there is no connection to sensor 2 input,

the status of BACKUP_VALUE is Bad and the

value is undefined.

Parameters Related to Limit Switches

Parameters whose names begin with “LIMSW”

store the settings for limit switch signals output

to DI function blocks. The transducer block

has 4 limit switches numbered from 1 to 4, and

these parameters determine the specifications

of the respective switches. In the following

parameter names and descriptions, read the

number “1” as “2,” “3,” or “4” according to the

intended limit switch number.

LIMSW_1_VALUE_D

Stores the value and status of limit switch 1.

LIMSW_1_TARGET

Stipulates the value that should be compared

with the threshold. PRIMARY_VALUE_1,

PRIMARY_VALUE_2, SECONDARY_VALUE,

DIFFERENTIAL_VALUE, AVERAGE_VALUE,

or BACKUP_VALUE can be chosen.

LIMSW_1_SETPOINT

Stipulates the threshold of switching on limit

switch 1.

LIMSW_1_ACT_DIRECTION

Stipulates whether limit switch 1 should work as

a high limit switch or low limit switch.

LIMSW_1_HYSTERESIS

Stipulates the hysteresis of limit switch 1.

Parameters Related to Display

For a model with the Integral indicator, the

display information can be selected by

parameters that have names beginning with

“DISPLAY.” For the details of contents to be

displayed, refer to section 6.4.

DISPLAY_AI_OUT

Specify an AI block number or numbers to

select the AI blocks whose output values should

be displayed on the LCD. If two or more AI

blocks are selected, the respective values are

displayed in turn cyclically.

DISPLAY_ERROR

Select whether to display the error code on the

LCD. Selecting 1 (INHIBIT) will hide the error

code from the LCD even when an error occurs.

DISPLAY_WARNING

Select whether to display the warning code

on the LCD. Even if this parameter is set to

‘SHOW’, error code for warning will not be

shown when the functions themselves are

disabled by parameters WARNING_ENABLE_

#.

DISPLAY_ADDRESS

Select whether to display the device address on

the LCD.

DISPLAY_CYCLE

Sets the display refresh cycle.

Parameters Related to Warnings

Faults found as a result of self-diagnostics of

the YTA320 are categorized into errors and

warnings. Warnings can be hidden from the

LCD as necessary by changing the values of

the parameters below. Refer section 7.4 for the

notes on using Warning function.

WARNING_ENABLE_1, (2, 3, 4)

Switches on and off the generation of warnings.

Parameters Related to Input

Calibrations

The number “2” enclosed in parentheses

appearing in the following parameter names

and descriptions indicates that the preceding

number “1” should be read as “2” for the cases

of sensor 2, respectively.

CAL_STATE_1 (2)

Shows if user adjustment function for

Sensor1(2) input is invalid(User Cal off) or

valid(User cal on). Setting ‘2(Calibration Exec)’

will allow users to adjust the input.

IMPORTANT

If you changing the sensor type once after

making user adjustment function valid, re-do

user adjustment or set ‘0(User Cal off)’ to CAL_

STATE_1 (2) to make the function off.