<8. Handling Caution>

8-4

IM 01C50T02-01E

Supply unit
The supply unit must be certified by a notify body

as FISCO model and following trapezoidal or

rectangular output characteristic is used.

Uo = 14 . . . 24 V (I.S. maximum value)

Io based on spark test result or other assessment,

ex. 133 mA for Uo = 15 V (Group IIC, rectangular

characteristic)

No specification of Lo and Co in the certificate and

on the label.

Cable
The cable used to interconnect the devices needs

to comply with the following parameters:

loop resistance R’: 15 . . . 150 Ω/km

inductance per unit length L’: 0.4 . . . 1 mH/km

capacitance per unit length C’: 80 . . . 200 nF/km

C’ = C’ line/line + 0.5 C’ line/screen, if both lines

are floating

or

C’ = C’ line/line + C’ line/screen, if the screen is

connected to one line

length of spur cable: max. 30 m (EEx ia IIC T4)

or 120 m (EEx ia IIB T4)

length of trunk cable: max. 1 km (EEx ia IIC T4)

or 1.9 km (EEx ia IIB T4)

Terminators
The terminator must be certified by a notify body as

FISCO model and at each end of the trunk cable

an approved line terminator with the following

parameters is suitable:

R = 90 . . . 100 Ω

C = 0 . . . 2.2 µF.

The resistor must be infallible according to IEC

60079-11. One of the two allowed terminators might

already be integrated in the associated apparatus

(bus supply unit).
FIELD INSTRUMENTS
Intrinsically safe ratings of the transmitter (FIELD

INSTRUMENTS) are as follows:
Supply/output circuit

EEx ia IIC T4

Maximum Voltage (Ui) = 17.5 V

Maximum Current (Ii) = 360 mA

Maximum Power (Pi) = 2.52 W

Internal Capacitance (Ci) = 1.5 nF

Internal Inductance (Li) = 8µH

EEx ia IIB T4

Maximum Voltage (Ui) = 17.5 V

Maximum Current (Ii) = 380 mA

Maximum Power (Pi) = 5.32 W

Internal Capacitance (Ci) = 1.5 nF

Internal Inductance (Li) = 8 µH

Sensor circuit

EEx ia IIC T4

Maximum Voltage (Uo) = 7.7 V

Maximum Current (Io) = 70 mA

Maximum Power (Po) = 140 mW

External Capacitance (Co) = 1.6 µF

External Inductance (Lo) = 7.2 mH

Number of Devices
The number of devices (max. 32) possible on a

fieldbus link depends on factors such as the power

consumption of each device, the type of cable used,

use of repeaters, etc.
(2) Entity Model

Non-Hazardous

Locations

Hazardous Locations

F0803.ai

Terminator

Ex i

Field Instruments

(Passive)

Hand-

held-

Terminal

Supply Unit

Terminator

Data

U

U

I

YTA

1 23 45

Supply

Sensor

I.S. fieldbus system complying with Entity

model

I.S. values Power supply-field device:

Po ≤ Pi, Uo ≤ Ui, Io ≤ Ii

Calculation of max. allowed cable length:

Ccable ≤ Co - Σci - Σci (Terminator)

Lcable ≤ Lo - ΣLi

FIELD INSTRUMENTS
Intrinsically safe ratings of the transmitter (FIELD

INSTRUMENTS) are as follows:

Supply/output circuit

EEx ia IIC T4

Maximum Voltage (Ui) = 24.0 V

Maximum Current (Ii) = 250 mA

Maximum Power (Pi) = 1.2 W

Internal Capacitance (Ci) = 1.5 nF

Internal Inductance (Li) = 8 µH