A4-3 – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 79

Advertising
background image

<Appendix 4. PID Block>

A4-3

IM 01C50T02-01E

Index Parameter Name

Default

(factory setting)

Write

Valid Range

Description

32

RCAS_IN

0

Remote setpoint set from a computer, etc.

33

ROUT_IN

0

Remote control output value set from a

computer, etc.

34

SHED_OPT

0

Action to be performed in the event of mode

shedding. SHED_OPT defines the changes

to be made to MODE.BLK.target and MODE.

BLK.actual when the value of RCAS_IN.status

or ROUT_IN.status becomes Bad if .MODE_

BLK.actual = RCas or ROut. See Section

A4.17.1 for details.

35

RCAS_OUT

0

Remote setpoint sent to a computer, etc.

36

ROUT_OUT

0

Remote control output value

37

TRK_SCALE

100

0

1342

1

MAN

Upper and lower scale limits used to convert

the output tracking value (TRK_VAL) to non-

dimensional.

38

TRK_IN_D

0

Switch for output tracking. See Section A4.12

for details.

39

TRK_VAL

0

Output tracking value (TRK_VAL) When

MODE_BLK.actual = LO, the value scaled

from the TRK_VAL value is set in OUT.

40

FF_VAL

0

Feedforward input value.

The FF_VAL value is scaled to a value with

the same scale as for OUT, multiplied by the

FF_GAIN value, and then added to the output

of the PID computation.

41

FF_SCALE

100

0

1342

1

MAN

Scale limits used for converting the FF_VAL

value to a non-dimensional value.

42

FF_GAIN

0

MAN

Gain for FF_VAL

43

UPDATE_EVT

Same as that for an AI block.

44

BLOCK_ALM

Same as that for an AI block.

45

ALARM_SUM

Enable

Same as that for an AI block.

46

ACK_OPTION

0xffff

Same as that for an AI block.

47

ALARM_HYS

0.5%

0 to 50%

Hysteresis for alarm detection and resetting

to prevent each alarm from occurring and

recovering repeatedly within a short time.

48

HI_HI_PRI

0

0 to 15

Priority order of HI_HI_ALM alarm

49

HI_HI_LIM

+INF

PV_SCALE

Setting for HI_HI_ALM alarm

50

HI_PRI

0

0 to 15

Priority order of HI_ALM alarm

51

HI_LIM

+INF

PV_SCALE

Setting for HI_ALM alarm

52

LO_PRI

0

0 to 15

Priority order of LO_ALM alarm

53

LO_LIM

-INF

PV_SCALE

Setting for LO_ALM alarm

54

LO_LO_PRI

0

0 to 15

Priority order of LO_LO_ALM alarm

55

LO_LO_LIM

-INF

PV_SCALE

Setting for LO_LO_ALM alarm

56

DV_HI_PRI

0

0 to 15

Priority order of DV_HI_ALM alarm

57

DV_HI_LIM

+INF

Setting for DV_HI_ALM alarm

58

DV_LO_PRI

0

0 to 15

Priority order of DV_LO_ALM alarm

59

DV_LO_LIM

-INF

Setting for DV_LO_ALM alarm

60

HI_HI_ALM

Alarm that is generated when the PV value

has exceeded the HI_HI_LIM value and

whose priority order* is defined in HI_HI_PRI.

* Priority order: Only one alarm is generated

at a time. When two or more alarms occur

at the same time, the alarm having the

highest priority order is generated. When

the PV value has decreased below [HI_HI_

LIM -ALM_HYS], HI_HI_ALM is reset.

Advertising