<7. Errors and Warnings>

7-3

IM 01C50T02-01E

Table 7.2

Warnings

Code

Displayed

on LCD

Indication of DEVICE_

STATUS_#

Cause

Remedy

AL100

AI1 in O/S mode

The actual mode of the AI1 block

is O/S.

See Table 7.3.

AL101

AI1 in MAN mode

The actual mode of the AI1 block

is Man.

Set the target mode of AI1 to Auto.

AL102

AI1 in Simulate Active

SIMULATE of the AI1 block is

Active.

Set SIMULATE of AI1 to Disabled.

AL103

AI1 Non-Scheduled

Execution of AI1 is not scheduled.

Include AI1 in the schedule (by setting

FB_START_ENTRY.#.)

AL104

AI2 in O/S mode

The actual mode of the AI2 block

is O/S.

See Table 7.3.

AL105

AI2 in MAN mode

The actual mode of the AI2 block

is Man.

Set the target mode of AI2 to Auto.

AL106

AI2 in Simulate active

SIMULATE of the AI2 block is

Active.

Set SIMULATE of AI2 to Disabled.

AL108

AI3 in O/S mode

The actual mode of the AI3 block

is O/S.

See Table 7.3.

AL109

AI3 in MAN mode

The actual mode of the AI3 block

is Man.

Set the target mode of AI3 to Auto.

AL110

AI3 in Simulate active

SIMULATE of the AI3 block is

Active.

Set SIMULATE of AI3 to Disabled.

AL112

AI4 in O/S mode

The actual mode of the AI4 block

is O/S.

See Table 7.3.

AL113

AI4 in MAN mode

The actual mode of the AI4 block

is Man.

Set the target mode of AI4 to Auto.

AL114

AI4 in Simulate active

SIMULATE of the AI4 block is

Active.

Set SIMULATE of AI4 to Disabled.

AL116

DI1 in O/S mode

The actual mode of the DI1 block

is O/S.

See Table 7.3.

AL117

DI1 in MAN mode

The actual mode of the DI1 block

is Man.

Set the target mode of DI1 to Auto.

AL118

DI1 in Simulate active

SIMULATE_D of the DI1 block is

Active.

Set SIMULATE_D of DI1 to Disabled.

AL120

DI2 in O/S mode

The actual mode of the DI2 block

is O/S.

See Table 7.3.

AL121

DI2 in MAN mode

The actual mode of the DI2 block

is Man.

Set the target mode of DI2 to Auto.

AL122

DI2 in Simulate active

SIMULATE_D of the DI2 block is

Active.

Set SIMULATE_D of DI2 to Disabled.

AL124

DI3 in O/S mode

The actual mode of the DI3 block

is O/S.

See Table 7.3.

AL125

DI3 in MAN_mode

The actual mode of the DI3 block

is Man.

Set the target mode of DI3 to Auto.

AL126

DI3 in Simulate active

SIMULATE_D of the DI3 block is

Active.

Set SIMULATE_D of DI3 to Disabled.

AL128

DI4 in O/S mode

The actual mode of the DI4 block

is O/S.

See Table 7.3.

AL129

DI4 in MAN mode

The actual mode of the DI4 block

is Man.

Set the target mode of DI4 to Auto.

AL130

DI4 in Simulate active

SIMULATE_D of the DI4 block is

Active.

Set SIMULATE_D of DI4 to Disabled.

AL132

PID1 in O/S

The actual mode of the PID1 block

is O/S.

See Table 7.3.

AL140

PID1 in Bypass active

The bypass action for PID1 is

active.

Reset BYPASS of PID1 to off.

AL142

PID2 in O/S mode

The actual mode of the PID2 block

is O/S.

See Table 7.3.