<Appendix 2. Parameters for Basic Settings, and How to Make and Change the Settings>

A2-6

IM 01C50T02-01E

(5) Setting the Low Cut-off Level
Set the low cut-off level such that the output will be

cut off to zero when it is below the low cut-off level.

Access the parameter LOW_CUT, and set the low cut-

off level.

Access the parameter IO_OPTS, and set

Low cutoff

to on (true). Resetting

Low cutoff to off (false) disables

the low cut-off function.

(6) Setting the Damping Time Constant

Access the parameter PV_FTIME, and set the time

constant (in seconds) of the first-order lag filter.

(7) Carrying Out the Simulation
You can carry out a simulation for an AI block

by manually setting the input value (within the

measurement range) and status.

Access the

Simulate Status component of the

parameter SIMULATE, and set the code of the desired

status to be set in simulation mode.

Access the

Simulate En/Disable component of the

parameter SIMULATE, and enable or disable the

simulation:

2 = Active

1 = Disable

Access the

Simulate Value component of the

parameter SIMULATE, and set the desired value.

An AI block performs the specified actions using:

• Values of

Simulate Status and Simulate Value

in SIMULATE as its input value and status when

the

Simulate En/Disable value is 2.

• Values of

Transducer Status and Transducer

Value in SIMULATE as its input value and

status when the

Simulate En/Disable value is

1.

See Section 6.3 for further details of the simulation

function.

A2.5 Setting Up DI Blocks

DI blocks are used to output limit switch signals

from the transducer block. Since each of the four DI

blocks in a YTA320 has independent parameters,

set the parameters for each DI block you use. The

following shows the procedure to set up the DI1

block for example.

(1) Setting the Channel
Specify the limit switch whose signal should be

input from the transducer block.

Access the parameter CHANNEL, and set the number

corresponding to the limit switch whose signal you want

to input:

7 = LIMSW_1_VALUE_D (Limit switch 1)

8 = LIMSW_2_VALUE_D (Limit switch 2)

9 = LIMSW_3_VALUE_D (Limit switch 3)

10 = LIMSW_4_VALUE_D (Limit switch 4)

(2) Setting the Damping Time Constant

Access the parameter PV_FTIME, and set the delay

time in seconds, which is the time period by which a

change in output should be delayed after a change in

input.

(3) Carrying Out the Simulation
You can carry out a simulation for a DI block

by manually setting the input value (within the

measurement range) and status.

Access the

Simulate Status component of the

parameter SIMULATE_D, and set the code of the

desired status to be set in simulation mode.

Access the

Simulate En/Disable component of the

parameter SIMULATE_D, and enable or disable the

simulation:

2 = Active

1 = Disable

Access the

Simulate Value component of the

parameter SIMULATE_D, and set the desired value.

A DI block performs the specified actions using:

• Values of

Simulate Status and Simulate Value

in SIMULATE_D as its input value and status

when the

Simulate En/Disable value is 2.

• Values of

Transducer Status and Transducer

Value in SIMULATE_D as its input value and

status when the

Simulate En/Disable value is

1.

See Section 6.3 for further details of the simulation

function.