<Appendix 2. Parameters for Basic Settings, and How to Make and Change the Settings>

A2-1

IM 01C50T02-01E

Appendix 2. Parameters for Basic

Settings, and How to Make

and Change the Settings

A2.1 Basic Settings and Corresponding Parameters

To Do This

Corresponding Parameters

Outline of Procedure

Set the tag numbers

Set the physical device tag number and each block's tag

number. Up to 32 alphanumeric characters can be set for

each. See Section 5.4 for details.

Make input sensor

settings

SENSOR_TYPE_1

SENSOR_CONNECTION_1

SENSOR_TYPE_2

SENSOR_CONNECTION_2

in the transducer block

Select the input sensor type and set the number of connection

wires, for each of sensors 1 and 2.

Set up a limit switch

LIMSW_1_TARGET

LIMSW_1_SETPOINT

in the transducer block

For limit switch 1, select the temperature to be monitored,

select the switch type (high-limit or low-limit switch), and set

the hysteresis and threshold.

Select inputs to AI and

DI blocks

CHANNEL

in each of AI and DI blocks

Select an output of the transducer block to be input to each of

the AI and DI blocks.

Set the measurement

ranges

XD_SCALE

in each AI block

For each AI block, set the range of the input from the

transducer block corresponding to 0% and 100% input levels

for the calculation inside the AI block. Before the transmitter is

shipped from the factory, these input range limits are set to the

0% and 100% range values specified by the customer when

ordered.
Set 3 data items: the unit of the input range, input value at 0%

input level (lower limit of calibrated range), and input value at

100% input level (upper limit of calibrated range).

Set output scales and

unit

OUT_SCALE

in each AI block

For each AI block, set the output scale corresponding to 0%

and 100% output levels for the calculation inside the AI block.

A different unit and range from those of the calibrated range

can be set by using the scaling calculation inside the block.
Set 3 data items: the unit of the output scale, output value at

0% output level (lower output scale limit), and output value at

100% output level (upper output scale limit).

Set the scale range and

unit of built-in indicator

[L_TYPE= Indirect/Indirect

SQRT]

OUT_SCALE

in the AI block or each of the AI

blocks whose outputs are to be

indicated

[L_TYPE= Direct]

XD_SCALE

In the AI block or each of the AI

blocks whose outputs are to be

indicated

When output mode L_TYPE is set to Indirect or Indirect

SQRT, the scales and units set in OUT_SCALE's above apply

to those of the indicator.

When output mode L_TYPE is set to Direct, the scales and

units set in XD_SCALE's above apply to those of the indicator.
The value to be displayed is within a range from −9999.9 to

9999.9.

Set the output modes

L_TYPE

in each AI block

Select the type of calculation performed in each AI block from

the following.

Direct: Outputs the value input from the transducer block

through filtering without performing the scaling and

square root extraction.

Indirect: Performs proportional scaling for the value input

from the transducer block through filtering, and then

outputs the result.

IndirectSQRT: Extracts the square root of the value input

from the transducer block through filtering, and then

outputs it.