<8. Handling Caution>

8-9

IM 01C50T02-01E

The allowed voltage Uo of the associated apparatus

used to supply the bus is limited to the range of 14

V dc to 24 V dc. All other equipment connected to

the bus cable has to be passive, meaning that the

apparatus is not allowed to provide energy to the

system, except to a leakage current of 50 µA for

each connected device.
Supply unit
Trapezoidal or rectangular output characteristic only

Uo = 14...24 V (I.S. maximum value)

Io according to spark test result or other

assessment, e.g. 133 mA for Uo = 15 V (Group

IIC, rectangular characteristic) No specification

of Lo and Co in the certificate and on the label.

Cable
The cable used to interconnect the devices needs

to comply with the following parameters:

loop resistance R’: 15...150 Ω/km

inductance per unit length L’: 0.4...1 mH/km

capacitance per unit length C’: 80...200 nF/km

C’=C’ line/line+0.5 C’ line/screen, if both lines

are floating

or

C’=C’ line/line+C’ line/screen, if the screen is

connected to one line

length of spur cable: max. 30 m (Group IIC) or

120 m (Group IIB)

length of trunk cable: max. 1 km (Group IIC) or

1.9 km (Group IIB)

Terminators
At each end of the trunk cable an approved line

terminator with the following parameters is suitable:

R = 90...100 Ω

C = 0...2.2 F

The resistor must be infallible according to IEC

60079-11. One of the two allowed terminators might

already be intergrated in the associated apparatus

(bus supply unit)
System evaluations
The number of passive device like transmitters,

actuators, hand held terminals connected to

a single bus segment is not limited due to I.S.

reasons. Furthermore, if the above rules are

respected, the inductance and capacitance of the

cable need not to be considered and will not impair

the intrinsic safety of the installation.

SAFE AREA

HAZARDOUS AREA

F0808.ai

Terminator

(FISCO Model)

Ex i

Field Instruments

(Passive)

Hand-

held-

Terminal

Supply Unit

(FISCO Model)

Terminator

Data

U

U

I

I.S. fieldbus system complying with FISCO model

Installation Diagram

(Nonincendive, Division 2 Installation)

Non Hazardous Location

Hazardous Location

F0809.ai

Terminator

Transmitter

Temperature

Transmitter

Terminator

Transmitter

1

2

3

4

5

SUPPLY

FM Approved Associated

Nonincendive Field Wiring Apparatus

Vt or Voc

It or Isc

Ca

La

(Nonincendive)

Power Supply

SENSOR

*1:

Dust-tight conduit seal must be used when installed in

Class II and Class III environments.

*2:

Installation should be in accordance with and the National

Electrical Code® (ANSI/NFPA 70) Sections 504 and 505.

*3:

The configuration of Associated Nonincendive Field

Wiring Apparatus must be FM Approved.