Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 40

Advertising
background image

<7. Errors and Warnings>

7-9

IM 01C50T02-01E

Table 7.11

Example of Warning Masking Settings

Case

Device Configurations

WARNING_

ENABLE_1

WARNING_

ENABLE_2

WARNING_

ENABLE_3

WARNING_

ENABLE_4

1

Sensor 2 is not used. Only AI1 is used.

0x7800 0000

0x0000 0000

0x6000 0000

0x2000 0000

2

Sensors 1 and 2 are used.

AI1 and AI2 are used.

0x7f00 0000

0x0000 0000

0x6060 0000

0x3000 0000

3

Sensors 1 and 2 are used.

AI1 and DI1 are used.

0x7800 7000

0x0000 0000

0x6060 0000

0x2000 0000

Table 7.12

Types of Warnings Displayed in Each of Cases 1 to 3

Parameter

Warning

Bit

Case 1

Case 2

Case 3

WARNING_

ENABLE_1

AI1 in O/S mode (AL100)

0x4000 0000

AI1 in MAN mode (AL101)

0x2000 0000

AI1 in Simulate active (AL102)

0x1000 0000

AI1 Non-Scheduled (AL103)

0x0800 0000

AI2 in O/S mode (Al104)

0x0400 0000

AI2 in MAN mode (AL105)

0x0200 0000

AI2 in Simulate active (AL106)

0x0100 0000

AI3 in O/S mode (AL108)

0x0040 0000

AI3 in MAN mode (Al109)

0x0020 0000

AI3 in Simulate active (AL110)

0x0010 0000

AI4 in O/S mode (AL112)

0x0004 0000

AI4 in MAN mode (Al113)

0x0002 0000

AI4 in Simulate active (AL114)

0x0001 0000

DI1 in O/S mode (AL116)

0x0000 4000

DI1 in MAN mode (AL117)

0x0000 2000

DI1 in Simulae active (AL118)

0x0000 1000

DI2 in O/S mode (AL120)

0x0000 0400

DI2 in MAN mode (AL121)

0x0000 0200

DI2 in Simulate active (AL122)

0x0000 0100

DI3 in O/S mode (AL124)

0x0000 0040

DI3 in MAN mode (AL125)

0x0000 0020

DI3 in Simulate active (AL126)

0x0000 0010

DI4 in O/S mode (AL128)

0x0000 0004

DI4 in MAN mode (AL129)

0x0000 0002

DI4 in Simulate active (AL130)

0x0000 0001

WARNING_

ENABLE_2

PID1 in O/S mode (AL132)

0x2000 0000

PID1 in Bypass active (AL140)

0x0020 0000

PID2 in O/S mode (AL142)

0x0008 0000

PID2 in Bypass active (AL150)

0x0000 0800

WARNING_

ENABLE_3

Sensor1 Temp Too High (AL160)

0x4000 0000

Sensor1 Temp Too Low (AL161)

0x2000 0000

Sensor2 Temp Too High (AL170)

0x0040 0000

Sensor2 Temp Too Low (AL171)

0x0020 0000

WARNING_

ENABLE_4

Stop Detection of Sensor Burnout (AL190)

0x4000 0000

Illegal Unit of AI1 (AL191)

0x2000 0000

Illegal Unit of AI2 (AL192)

0x1000 0000

Illegal Unit of AI3 (AL193)

0x0800 0000

Illegal Unit of AI4 (AL194)

0x0400 0000

Default Address Mode (AL198)

0x0040 0000

Advertising