<8. Handling Caution>

8-7

IM 01C50T02-01E

*1: The production year

The third figure from the left of the serial number shows

the year of production. The relation between the third

figure and the production year is shown below.

Third figure

D

E

F

G

H

J

K

Production year 2004 2005 2006 2007 2008 2009 2010

For example, the production year of the product engraved

in “NO.” column on the name plate as follows is 2007.

C2G218541

2007

*2: “180-8750” is a zip code which represents the following

address.

2-9-32 Nakacho, Musashino-shi, Tokyo Japan

*3: The identification number of Notified Body

8.1.3 FM Certification

A) FM Explosionproof Type
Caution for FM Explosionproof type

Note 1. Model YTA320-F /FF1 temperature

transmitters are applicable for use in

hazardous locations:

* Applicable Standard: FM 3600, FM 3615,

FM 3810, NEMA250

* Explosionproof for Class I, Division 1,

Groups A, B, C, and D.

* Dust-ignitionproof for Class II/III, Division

1, Groups E, F and G.

* Enclosure rating: NEMA 4X.

* Temperature Class: T6

* Ambient Temperature: –40 to 60°C

* Supply Voltage: 32 V dc max.

Note 2. Wiring

* All wiring shall comply with National

Electrical Code ANSI/NEPA70 and Local

Electrical Codes.

* “FACTORY SEALED, CONDUIT SEAL

NOT REQUIRED”.

Note 3. Operation

* Keep strictly the “WARNING” on the

nameplate attached on the transmitter.

WARNING: OPEN CIRCUIT BEFORE

REMOVING COVER.

“FACTORY SEALED, CONDUIT SEAL

NOT REQUIRED”.

INSTALL IN ACCORDANCE WITH THE

INSTRUCTION MANUAL IM 1C50B1.

* Take care not to generate mechanical

spark when access to the instrument and

peripheral devices in hazardous location.

Note 4. Maintenance and Repair

* The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void

Factory Mutual Explosionproof Approval.

B) FM Intrinsically Safe Type
Model YTA Series temperature transmitters with

optional code /FS15.

* Applicable Standard: FM 3600, FM 3610,

FM 3611, FM 3810, NEMA250, ANSI/ISA-

60079-0, ANSI/ISA-60079-11

• FM Intrinsically Safe Approval

[Entity Model]

Class I, II & III, Division 1, Groups A, B, C, D, E,

F & G, Temperature Class T4 Ta=60°C, Type

4X and Class I, Zone 0, AEx ia IIC, Temperature

Class T4 Ta=60°C, Type 4X

[FISCO Model]

Class I, II & III, Division 1, Groups A, B, C, D, E,

F & G, Temperature Class T4 Ta=60°C, Type

4X and Class I, Zone 0, AEx ia IIC, Temperature

Class T4 Ta=60°C, Type 4X

• Nonincendive Approval

Class I, Division 2, Groups A, B, C & D and

Class I, Zone 2, Group IIC

Class II, Division 2, groups F & G,

Temperature Class: T4

Enclosure: NEMA 4X

• Electrical Connection: 1/2 NPT female

• Caution for FM Intrinsically safe type. (Following

contents refer to “DOC. No. IFM018-A12 p.1,

p.2, p.3, and p.3-1.”)