<8. Handling Caution>

8-1

IM 01C50T02-01E

8. Handling Caution

This chapter describes important cautions

regarding the installation of explosion protected

type for FOUNDATION Fieldbus YTA transmitters.

For JIS flameproof type, refer to IM 01C50B01-01E.

CAUTION

This instrument is tested and certified as

intrinsically safe type or explosionproof

type. Please note that the construction of

the instrument, installation, external wiring,

maintenance or repair is strictly restricted,

and non-observance or negligence of these

restriction would result dangerous condition.

WARNING

To preserve the safety of explosionproof

equipment requires great care during mounting,

wiring, and piping. Safety requirements also

place restrictions on maintenance and repair

activities. Please read the following sections very

carefully.

Sensor

Sensor

Non-hazardous

Location

Equipment

42 V DC Max.

4 to 20 mA DC

Signal

NON-HAZARDOUS

LOCATIONS

HAZARDOUS LOCATIONS DIVISION 1

50 cm Max.

Sealing Fitting

Conduit

Non-hazardous

Location

Equipment

42 V DC Max.

4 to 20 mA DC

Signal

NON-HAZARDOUS

LOCATIONS

HAZARDOUS LOCATIONS DIVISION 2

Sealing Fitting

Sealing Fitting

50 cm Max.

Certified/Listed Temperature Sensor

Explosionproof Class I, Groups C and D

Dustignitionproof Class II, Groups E, F and G, Class III
Wiring method shall be suitable for the specified hazardous locations.

YTA Series

YTA Series

Conduit

F0801.ai

Certified/Listed Temperature Sensor

Explosionproof Class I, Groups C and D

Dustignitionproof Class II, Groups E, F and G, Class III
Wiring method shall be suitable for the specified hazardous locations.

8.1 Installation of

Explosionproof Type

Transmitters

8.1.1 CSA Certification

A) CSA Explosionproof Type
Caution for CSA Explosionproof type

Note 1. YTA320-F/CF1 temperature transmitters

are applicable for use in hazardous

locations:

Certificate 1089576

[For CSA C22.2]

* Applicable Standard: C22.2 No.0, C22.2

No.0.4, C22.2 No.25, C22.2 No.30, C22.2

No.94, C22.2 No.142, C22.2 No.157,

C22.2 No.213, C22.2 No.1010.1

* Explosionproof for Class I, Division 1,

Groups B, C and D.

* Dust-ignitionproof for Class II, Groups E, F

and G, Class III.

* Encl “Type 4X”

* Temperature Class: T6

* Ambient Temperature: –40 to 60°C

* Supply Voltage: 32 V dc max