<8. Handling Caution>

8-3

IM 01C50T02-01E

* When combined with FISCO model IIC

barrier

Ui = 17.5 V, Ii = 360 mA, Pi = 2.52 W,

Ci = 1.5 nF, Li = 8 µH

* When combined with barrier

Ui = 24.0 V, Ii = 250 mA, Pi = 1.2 W,

Ci = 1.5 nF, Li = 8 µH

• EEx ia IIB T4

Type of Protection and Marking Code:

EEx ia IIB T4

Group: II

Category: 1G

Ambient Temperature: –40 to 60°C

Degree of Protection of the Enclosure: IP67

Electrical Data

* When combined with FISCO model IIB

barrier

Ui = 17.5 V, Ii = 380 mA, Pi = 5.32 W,

Ci = 1.5 nF, Li = 8 µH

[Sensor circuit]

Uo = 7.7 V, Io = 70 mA, Po = 140 mW,

Co = 1.6 µF, Li = 7.2 mH

• The above parameters apply when one of

the two conditions below is given:

- the total Li of the external circuit

(excluding the cable) is < 1% of the Lo

value or

- the total Ci of the external circuit

(excluding the cable) is < 1% of the Co

value.

• The above parameters are reduced to

50% when both of the two conditions

below are given:

- the total Li of the external circuit

(excluding the cable) is ≥ 1% of the Lo

value and

- the total Ci of the external circuit

(excluding the cable) is ≥ 1% of the Co

value.

• The reduced capacitance of the external

circuit (including cable) shall not be

greater than 1µF for Group IIB and 600nF

for Group IIC.

Note 3. Installation

* All wiring shall comply with local

installation requirements. (Refer to the

installation diagram)

Note 4. Maintenance and Repair

* The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void

KEMA Intrinsically safe Certification.

Note 5. Special condition for safe use

* Because the enclosure of the Temperature

Transmitter is made of aluminum, if it

is mounted in an area where the use of

category 1G apparatus is required, it must

be installed such, that, even in the event

of rare incidents, ignition source due to

impact and friction sparks are excluded.

Note 6. Installation instructions

* From the safety point of view the circuit

shall be considered to be connected to

earth.

As this deviates from the FISCO system

in accordance with IEC TS 60079-27 care

has to be taken that the (local) installation

requirements are taken into account as

well.

(1) FISCO Model

Non-Hazardous

Locations

Hazardous Locations

F0802.ai

Terminator

(FISCO Model)

Ex i

Field Instruments

(Passive)

Hand-

held-

Terminal

Supply Unit

(FISCO Model)

Terminator

Data

U

U

I

YTA

1 23 45

Supply

Sensor

I.S. fieldbus system complying with FISCO
The criterion for such interconnection is that the

voltage (Ui), the current (Ii) and the power (Pi),

which intrinsically safe apparatus can receive,

must be equal or greater than the voltage (Uo),

the current (Io) and the power (Po) which can be

provided by the associated apparatus (supply unit).

In addition, the maximum unprotected residual

capacitance (Ci) and inductance (Li) of each

apparatus (other than the terminators) connected

to the fieldbus line must be equal or less than 5 nF

and 10 µH respectively.