<Appendix 1. List of Parameters for Each Block of the YTA>

A1-2

IM 01C50T02-01E

Relative

Index

Index Parameter Name

Factory Default

Write

Mode

Explanation

16

1016 RESTART

Allows a manual restart to be initiated. Several

degrees of restart are possible. They are 1: Run,

2: Restart resource, 3: Restart with defaults defined

in FF specification*

1

, and 4: Restart processor.

17

1017 FEATURES

Soft write lock

supported

Report

supported

Used to show supported resource block options.

18

1018 FEATURE_SEL

Soft write lock

supported

Report

supported

Used to select resource block options.

19

1019 CYCLE_TYPE

Scheduled

Identifies the block execution methods available for

this resource.

bit0: Scheduled

bit1: Event driven

bit2: Manufacturer specified

20

1020 CYCLE_SEL

Scheduled

Used to select the block execution method for this

resource.

21

1021 MIN_CYCLE_T

3200 (100ms)

Time duration of the shortest cycle interval of which

the resource is capable.

22

1022 MEMORY_SIZE

0

Available configuration memory in the empty

resource. To be checked before attempting a

download.

23

1023 NV_CYCLE_T

0

Interval between writing copies of NV parameters to

non-volatile memory. Zero means never.

24

1024 FREE_SPACE

0

Percent of memory available for further

configuration. YTA has zero which means a

preconfigured resource.

25

1025 FREE_TIME

0

Percent of the block processing time that is free to

process additional blocks. YTA does not support

this.

26

1026 SHED_RCAS

Time duration at which to give up on computer

writes to function block RCas locations. YTA does

not support this.

27

1027 SHED_ROUT

Time duration at which to give up on computer

writes to function block ROut locations. YTA does

not support this.

28

1028 FAULT_STATE

1: Clear

Condition set by loss of communication to an

output block, failure promoted to an output block

or a physical contact. When fail-safe condition is

set, Then output function blocks will perform their

FSAFE actions.

29

1029 SET_FSTATE

1: OFF

Allows the fail-safe condition to be manually

initiated by selecting Set.

30

1030 CLR_FSTATE

1: OFF

Writing a Clear to this parameter will clear the

device fail-safe state if the field condition, if any, has

cleared.

31

1031 MAX_NOTIFY

3

Maximum number of unconfirmed notify messages

possible.

32

1032 LIM_NOTIFY

3

Auto

Maximum number of unconfirmed alert notify

messages allowed.

33

1033 CONFIRM_TIME

640000

Auto

The minimum time between retries of alert reports.

34

1034 WRITE_LOCK

1: Not Locked

Auto

If set, no writes from anywhere are allowed, except

to clear WRITE_LOCK. Block inputs will continue to

be updated

35

1035 UPDATE_EVT

This alert is generated by any change to the static

data.