A4.5.1 velocity type output action, A4.6 direction of control action, A4.7 control action bypass – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 81: A4.8 feed-forward, A4.9 block modes, A4.5.1, A4.6, A4.7, A4.8, A4.9

Advertising
background image

<Appendix 4. PID Block>

A4-5

IM 01C50T02-01E

A4.5.1 Velocity Type Output Action

The PID block determines the value of the new

control output OUT by adding the change in control

output calculated in the current control period,

∆MVn, to the current read-back value of the MV,

MVRB (BKCAL_IN). This action can be expressed

as:

OUT = BKCAL_IN – ∆MVn'
∆MVn' = ΔMVn which is scaled by

PV_SCALE and OUT_SCALE

A4.6 Direction of Control Action

The direction of the control action is determined by

the Direct Acting setting in CONTROL_OPTS.

Value of Direct Acting

Resulting Action

True

The output increases when

the input PV is greater than

the setpoint SP.

False

The output decreases when

the input PV is greater than

the setpoint SP.

A4.7 Control Action Bypass

The PID control computation can be bypassed so

as to set the SP value in the control output OUT as

shown below. Setting BYPASS to “On” bypasses

the PID control computation.

Setpoint

Control

Feed-

forward

CAS_IN

Filter

IN

PV

BYPASS

SP

RCAS_IN

Output

OUT

FA0402.ai

A4.8 Feed-forward

Feed-forward is an action to add a compensation

output signal FF_VAL to the output of the PID

control computation, and is typically used for feed-

forward control. The figure below illustrates the

action.

PID

computation

FF_SCALE

OUT_SCALE

PV

OUT

FF_VAL

FF_GAIN

FA0403.ai

the change in

A4.9 Block Modes

The block mode is set in the parameter MODE-

BLK.

MODE_

BLK

Target

Stipulates the target mode to

which the PID block transfers.

Actual

Indicates the current mode of

the PID block.

Permitted Stipulates all the modes that

the PID block can enter. The

PID block is prohibited to

enter any mode other than

those set in this element.

Normal

Stipulates the mode in which

the PID block normally

resides.

There are eight modes for a PID block as shown

below.

Advertising
This manual is related to the following products: